Schneider Electric
M9F12403
Miniature circuit breaker (MCB), Multi9 C60N, 4P, 3A, D curve, 10kA (IEC/EN 60947-2)
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
Enviar solicitud de precio
1
Formas de pago:
Condiciones del producto:
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
Enviar solicitud de precio
Additional Information
- Part Number
- M9F12403
- UNSPSC
- 39121603
- Tariff Code
- 8536200020
- Country of Origin
- FR
Specifications
- Line Rated Current
- 3 A 50 °C EN/IEC 60947-2
- Curve Code
- D
- Number Of Protected Poles
- 4
- Network Type
- DC || AC
- Standards
- EN/IEC 60947-2
- Product Certifications
- EAC || CCC
- Product Or Component Type
- miniature circuit-breaker
- Product Name
- Multi9 C60
- Utilisation Category
- category A EN/IEC 60947-2
- Range
- Multi9
- Breaking Capacity
- 40 kA Icu <= 250 V DC EN/IEC 60947-2 || 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 || 20 kA Icu 240 V AC 50/60 Hz between phases EN/IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz between phases EN/IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 4P
- Device Application
- distribution
- Device Short Name
- C60N
- Trip Unit Technology
- thermal-magnetic
Complementary
- Network Frequency
- 50/60 Hz
- [Ics] Rated Service Breaking Capacity
- 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz || 16 kA 75 % EN/IEC 60947-2 - 240 V AC 50/60 Hz || 4.5 kA 75 % EN/IEC 60947-2 - 440 V AC 50/60 Hz || 40 kA 100 % EN/IEC 60947-2 - <= 250 V DC
- Height
- 81 mm
- Contact Position Indicator
- yes
- Earth-Leakage Protection
- separate block
- Mounting Support
- DIN rail
- 9 Mm Pitches
- 8
- Limitation Class
- 3
- Net Weight
- 0.48 kg
- Wire Stripping Length
- 14 mm top or bottom
- Control Type
- toggle
- Connections - Terminals
- tunnel type terminal top or bottom) 1-25 mm² - rigid || tunnel type terminal top or bottom) 1-25 mm² - flexible || tunnel type terminal top or bottom) 1-25 mm² - flexible with ferrule
- [Ui] Rated Insulation Voltage
- 500 V AC 50/60 Hz EN/IEC 60947-2
- Mounting Mode
- clip-on
- Electrical Durability
- 10000 cycles
- Mechanical Durability
- 20000 cycles
- Local Signalling
- ON/OFF indication
- [Uimp] Rated Impulse Withstand Voltage
- 6 kVEN/IEC 60947-2
- Color
- Gray
- Width
- 72 mm
- Provision For Padlocking
- padlockable
- Depth
- 72 mm
- Tightening Torque
- 2-2 N.m top or bottom
- Magnetic Tripping Limit
- 12 x In +/- 20 % AC || 17 x In +/- 20 % DC
- [Ue] Rated Operational Voltage
- 240 V AC 50/60 Hz between phases || 415 V AC 50/60 Hz between phases || 440 V AC 50/60 Hz between phases || <= 250 V DC
Environment
- Ambient Air Temperature For Operation
- -30-70 °C
- Tropicalisation
- 2 IEC 60068-1
- Ip Degree Of Protection
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Pollution Degree
- 3 EN/IEC 60947-2
- Ambient Air Temperature For Storage
- -40-80 °C
- Relative Humidity
- 95-95 % 55-55 °C
- Overvoltage Category
- IV
- Heat Dissipation
- 8.8-8.8 W 415 V - 3 A