Weidmuller

1335030000

UR20-PF-O-1DI-SIL
1335030000
1335030000
1335030000
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.
Oferta con plazo de entrega del fabricante
Entrega:Bajo pedido
El mejor precio:
€236.13

Additional Information

Part Number
1335030000

General Data

Air humidity (operation)
10% to 95%, non-condensing as per DIN EN 61131-2
Air humidity (storage)
10% to 95%, non-condensing as per DIN EN 61131-2
Air humidity (transport)
10% to 95%, non-condensing as per DIN EN 61131-2
Air pressure (operation)
≥ 795 hPa (height ≤ 2000 m) as per DIN EN 61131-2
Air pressure (storage)
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2
Air pressure (transport)
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2
Pollution severity
2
Shock
15 g over 11 ms, half sinus wave, acc. to IEC 60068-2-27
Surge voltage category
II
Test voltage
500 V
UL 94 flammability rating
V-0
Vibration resistance
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6, 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration as per IEC 60068-2-6

Approvals

Approvals
CULUS, CULUSEX, DEMKOATEX, EAC, FUSAFETY, IECEXULD, KOREANCERT, TUEV
ROHS
Conform
UL File Number Search
E141197

Dimensions And Weights

Width
11.5 mm
Width (inches)
0.453 inch
Height
120 mm
Height (inches)
4.724 inch
Depth
76 mm
Depth (inches)
2.992 inch
Mounting dimension - height
128 mm
Net weight
109 g

Connection Data

Type of connection
PUSH IN
Wire connection cross section, finely stranded, max.
1.5 mm²
Wire connection cross-section, finely stranded, min.
0.14 mm²
Wire cross-section, finely stranded, max. (AWG)
AWG 16
Wire cross-section, finely stranded, min. (AWG)
AWG 26
Wire cross-section, solid, max.
1.5 mm²
Wire cross-section, solid, max. (AWG)
AWG 16
Wire cross-section, solid, min.
0.14 mm²
Wire cross-section, solid, min. (AWG)
AWG 26

Safety-Related Data

MTTF
100 Years
Proportion of safety-related outages (SFF)
98 %
Safety category
SIL 3

Classifications

ETIM 6.0
EC001600
ETIM 7.0
EC001600
EClass 9.0
27-24-26-10
EClass 9.1
27-24-26-10
EClass 10.0
27-24-26-10

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

System Data

Field bus protocol
CANopen, DeviceNet, EtherCAT, EtherNet/IP, Modbus/TCP, PROFINET IRT, PROFIBUS DP-V1, POWERLINK
Galvanic isolation
Yes, between field and system bus
Interface
u-remote system bus
Module type
Safe power-feed module
Transmission speed of system bus, max.
48 Mbit

Temperatures

Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-20 °C ... +60 °C
Storage temperature
-40 °C ... +85 °C

Power Supply

Current consumption from I
35 mA
Feed current for I
8,050 mA
Supply voltage for outputs
24 V DC +20 %/ -15 %
Supply voltage system and inputs
24 V DC +20 %/ -15 %
Voltage supply
24 V DC +20 %/ -15 %, via the system bus