- Standards
- IEC/EN 60947-2, IEC/EN 60898-1
- Tripping Characteristic
- C
- Type of Residual Current
- standard version
- Rated Voltage (Ur)
- acc. to IEC 60947-2 690 V ACacc. to IEC 60947-2 500 V DCacc. to IEC 60898-1 400 V AC
- Rated Operational Voltage
- acc. to IEC 60898-1 400 V
- Operational Voltage
- Maximum 230/400 V ACMinimum 12 V AC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 690 V
- Rated Impulse Withstand Voltage (Uimp)
- 8 kV
- Input Voltage Type
- AC/DC
- Rated Current (In)
- 40 A
- Rated Operational Current (Ie)
- 40 A
- Rated Short-Circuit Capacity
- (230 V) 20 kA(400 V) 20 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (230 V) 36 kA(400 V) 4.5 kA
- Rated Conditional Short-Circuit Current (Inc)
- (230 V) 36 kA(400 V) 36 kA
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (240 / 415 V AC) 30 kA(254 / 440 V AC) 15 kA(400 / 690 V AC) 3 kA(125 V DC) 20 kA
- Frequency (f)
- 50 ... 60 Hz
- Rated Frequency (f)
- 50/60 Hz
- Power Loss
- 14.8 Wat Rated Operating Conditions per Pole 3.7 W
- Contact Position Indication
- ON / OFF / TRIP
- Energy Limiting Class
- 3
- Electrical Endurance
- 6000 cycle
- Mechanical Endurance
- 4000 cycle
- Number of Poles
- 4
- Number of Protected Poles
- 4
- Overvoltage Category
- IV
- Tightening Torque
- 3.5 N·m31 in·lb
- Release Type
- C
- Actuator Marking
- I / O
- Housing Material
- Insulation group I, RAL 7035
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position
- Any
- Recommended Screw Driver
- Pozidriv 2
- Accessories Available
- Yes
- Remarks
- Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw
- Connecting Capacity
- Flexible 0 … 50 mm²Rigid 0 … 70 mm²
- Terminal Type
- Screw Terminals