Eaton
167114
1 / 2
- Part Number
- 167114
- EAN
- 4015081636167
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Specifications
- Rated operational current for specified heat dissipation (In)
- 40 A
- 10.11 Short-circuit rating
- Is the panel builder's responsibility. The specifications for the switchgear must be observed.
- Permitted storage and transport temperature - min
- -35 °C
- 10.4 Clearances and creepage distances
- Meets the product standard's requirements.
- 10.12 Electromagnetic compatibility
- Is the panel builder's responsibility. The specifications for the switchgear must be observed.
- Mounting Method
- Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
- Amperage Rating
- 40 A
- 10.2.5 Lifting
- Does not apply, since the entire switchgear needs to be evaluated.
- Rated fault current - max
- .03 A
- Test circuit range
- 184 V AC - 250 V AC, 196 V AC - 305 V AC (UL)
- 10.2.3.1 Verification of thermal stability of enclosures
- Meets the product standard's requirements.
- Tripping time
- Non-delayed
- Fitted with:
- Interlocking device
- Rated residual making and breaking capacity
- 500 A
- Frequency rating
- 50 Hz / 60 Hz
- 10.8 Connections for external conductors
- Is the panel builder's responsibility.
- Fault current rating
- 30 mA
- Terminal protection
- Busbar tag shroud to BGV A3, ÖVE-EN 6
- Special features
- Current test marks as per inscription\nMaximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C\nThe maximum operating current of back-up fuse must not exceed the residual current circuit breaker's rated operational current
- Sensitivity type
- Pulse-current sensitive
- Ambient operating temperature - max
- 40 °C
- Heat dissipation per pole, current-dependent
- 3.9 W
- Climatic proofing
- 25-55 °C / 90-95% relative humidity according to IEC 60068-2
- Built-in depth
- 70.5 mm
- Short-circuit rating
- Max. admissible back-up fuse: 63 A gG/gL, 70 A class J fuse (UL)
- Features
- Additional equipment possible
- Lifespan, electrical
- 4000 operations
- Terminal capacity (cable)
- M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
- Connectable conductor cross section (solid-core) - min
- 1.5 mm²
- Contact position indicator color
- Red / green
- 10.9.3 Impulse withstand voltage
- Is the panel builder's responsibility.
- Number of poles
- Two-pole
- Terminal capacity (solid wire)
- 1.5 mm² - 35 mm²
- Ambient operating temperature - min
- -25 °C
- 10.6 Incorporation of switching devices and components
- Does not apply, since the entire switchgear needs to be evaluated.
- Rated short-circuit strength
- 10 kA with back-up fuse
- 10.5 Protection against electric shock
- Does not apply, since the entire switchgear needs to be evaluated.
- Mounting position
- As required
- Equipment heat dissipation, current-dependent
- 7.8 W
- 10.13 Mechanical function
- The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
- 10.2.6 Mechanical impact
- Does not apply, since the entire switchgear needs to be evaluated.
- 10.9.4 Testing of enclosures made of insulating material
- Is the panel builder's responsibility.
- Static heat dissipation, non-current-dependent
- 0 W
- Application
- Switchgear for export to North America (UL-listed)
- 10.3 Degree of protection of assemblies
- Does not apply, since the entire switchgear needs to be evaluated.
- Voltage rating (IEC/EN 60947-2)
- 240 V AC / 415 V AC
- Terminal capacity (stranded cable)
- 16 mm² (2x)
- Leakage current type
- A
- Frame
- 45 mm
- Built-in width (number of units)
- 35 mm (2 SU)
- Terminals (top and bottom)
- Lift terminals
- Heat dissipation capacity
- 0 W
- Ambient humdity range
- 5 - 95 %
- Impulse withstand current
- 250 A (8/20 μs) surge-proof
- Width in number of modular spacings
- 2
- 10.2.3.2 Verification of resistance of insulating materials to normal heat
- Meets the product standard's requirements.
- 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
- Meets the product standard's requirements.
- Lifespan, mechanical
- 10000 operations
- Status indication
- White / blue
- 10.9.2 Power-frequency electric strength
- Is the panel builder's responsibility.
- Connectable conductor cross section (solid-core) - max
- 35 mm²
- Degree of protection
- IP20, IP40 with suitable enclosure
- Rated short-time withstand current (Icw)
- 10 kA
- Overvoltage tested - max
- 530 V
- Pollution degree
- 2
- 10.7 Internal electrical circuits and connections
- Is the panel builder's responsibility.
- Connectable conductor cross section (multi-wired) - min
- 1.5 mm²
- Rated impulse withstand voltage (Uimp)
- 4 kV (1.2/50 µs)
- 10.10 Temperature rise
- The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
- Voltage rating (UL)
- 480Y/277 V, 60 Hz
- Connectable conductor cross section (multi-wired) - max
- 16 mm²
- Type
- FRCmM-NA\nResidual current circuit breakers\nType A
- 10.2.2 Corrosion resistance
- Meets the product standard's requirements.
- 10.2.4 Resistance to ultra-violet (UV) radiation
- Meets the product standard's requirements.
- 10.2.7 Inscriptions
- Meets the product standard's requirements.
- Surge current capacity
- .25 kA
- Permitted storage and transport temperature - max
- 60 °C
- Admissible back-up fuse overload - max
- 40 A gG/gL
- Rated fault current - min
- .03 A
- Pick-up current
- 22 mA
- Rated operational voltage (Ue) - max
- 277 V
- Rated insulation voltage (Ui)
- 440 V
General
- Model Code
- FRCMM-40/2/003-A-NA
- EAN
- 4015081636167
- Product Length/Depth
- 80 mm
- Product Height
- 71 mm
- Product Width
- 35 mm
- Product Weight
- .22 kg
- Compliances
- RoHS conform
- Certifications
- UL 1053
- Catalog Notes
- Protects against special forms of residual pulsating DC which have not been smoothed.
Altre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro