Schneider Electric

389FXCXC-120A

Power relay, SE Relays, 3PDT, 20A, 120 VAC, plug-in socket cover
389FXCXC-120A
389FXCXC-120A
389FXCXC-120A
389FXCXC-120A
389FXCXC-120A
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 10 Parts In-Stock da 1 Distributor

Additional Information

Part Number
389FXCXC-120A
UNSPSC
39122324
Country of Origin
CN

Specifications

Contacts Type And Composition
3 NO + 3 NC
Switch Function
3PDT
Product Or Component Type
power relay

Complementary

Input Voltage
120 V AC
Voltage Range
0.85...1.1 Uc AC
[Ie] Rated Operational Current
20 A at 150 V AC (on resistive load) conforming to UL || 15 A at 250 V AC (on resistive load) conforming to UL || 13 A at 28 V DC (on resistive load) conforming to UL || 20 A at 150 V AC (ballast) conforming to UL || 6.67 A at 277 V AC (ballast) conforming to UL || 20 A at 250 V AC (NO/NC) conforming to IEC || 15 A at 28 V DC (NO/NC) conforming to IEC
Input Resistance
1700 Ohm
Minimum Switching Current
100 mA 5 V DC
Connections - Terminals
Quick
Mounting Support
socket
Power Consumption In W
1.3-1.3 W DC
Contacts Material
silver alloy contacts
Power Consumption In Va
2-2 VA AC
Input Current
20 A
Drop-Out Voltage Threshold
>= 0.1 Uc AC/DC
Maximum Horse Power Rating
0.5 hp 120/240 V AC 50/60 Hz
Net Weight
84 g
Maximum Switching Voltage
300 V AC

Offer Sustainability

China Rohs Regulation
X
Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1406038EN
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Environment

Product Certifications
cURus || CSA || CE
Ambient Air Temperature For Operation
-30-55 °C
Ambient Air Temperature For Storage
-30-85 °C
Electrical Durability
100000 cycles resistive load || 50000 cycles resistive DC load
Mechanical Durability
5000000 cycles
Dielectric Strength
2200 V AC between coil and contact || 2200 V AC between poles || 1600 V AC between contacts

Documenti