VigiPacT RH99P is a front panel mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 220/240VAC 50/60Hz. It is a type A earth-leakage protection class. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a front panel switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.
Country of Origin
FR
Part Number
56273
Tariff Code
85364900
EAN
3303430562733
UNSPSC
39121601
Metodi di pagamento:
Migliore offerta da:
ITFornitore Automa.Net di fiducia
Disponibilità:
95 pz.
Disponibile
Aggiornato il: 21-11-2024
Garanzia:
12 mesi
Consegna stimata:
Su richiesta
Condizione:
Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Informazioni sulla spedizione
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Environment

Ambient Air Temperature For Operation
-35-70 °C
Electromagnetic Compatibility
conducted and radiated emissionsB CISPR 11 || conducted radio-frequency immunity test3 IEC 61000-4-6 || electrostatic discharge immunity test4 IEC 61000-4-2 || high-energy conducted susceptibility4 IEC 61000-4-5 || low-energy conducted susceptibility4 IEC 61000-4-4 || radiated susceptibility3 IEC 61000-4-3
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-55-85 °C
Relative Humidity
95-95 % 55-55 °C
Electrical Shock Protection Class
class II
Overvoltage Category
IV

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2310023EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2310023EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Ik Degree Of Protection
IK07 EN 50102
Mechanical Robustness
fire resistance IEC 60695-2-1 || IK protection 2 joulesIK07 EN 50102 || vibrations 13.2...100 Hz0.7 g || vibrations 2...13.2 Hz+/- 1 mm
Height
72 mm
Standards
EN/IEC 60947-2 Annex M || EN/IEC 60755 || UL 1053 || CAN/CSA C22.2 No. 144
Type Of Measurement
earth fault current internal measurement 80...100 %
Net Weight
0.3 kg
Tamperproof Of Settings
protected by sealable cover
Wire Stripping Length
auxiliary power supply: 7 mm || fault: 7 mm || relay test and fault reset: 7 mm || sensor: 7 mm || voltage presence: 7 mm
Connections - Terminals
auxiliary power supply terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || auxiliary power supply terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || auxiliary power supply terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || fault terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || fault terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || fault terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || relay test and fault reset terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || relay test and fault reset terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || relay test and fault reset terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || sensor terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || sensor terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || sensor terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12 || voltage presence terminal block 0.2-2.5 mm² flexible AWG 24...AWG 12 || voltage presence terminal block 0.2-2.5 mm² rigid AWG 24...AWG 12 || voltage presence terminal block 0.25-2.5 mm² flexible AWG 24...AWG 12
Cut-Out Dimensions
68 x 68 mm
Ip Degree Of Protection
on front face IP40 EN/IEC 60529 || on side parts IP30 EN/IEC 60529 || on connection terminals IP20 EN/IEC 60529
Test Function
local || remote test
Monitoring
electronics continuous) || power supply continuous) || relay/sensor link continuous)
Width
72 mm
Depth
78 mm
Tightening Torque
auxiliary power supply: 0.6-0.6 N.m || fault: 0.6-0.6 N.m || relay test and fault reset: 0.6-0.6 N.m || sensor: 0.6-0.6 N.m || voltage presence: 0.6-0.6 N.m

Specifications

Type Of Setting
selector
Reset
manual reset
Earth Leakage Current
0.03-30 A
Mounting Support
front panel
Range Compatibility
VigiPacT TOA earth leakage current sensor || VigiPacT A earth leakage current sensor || VigiPacT L earth leakage current sensor
Earth-Leakage Protection Class
type A
Network Rated Voltage
1000-1000 V - AC 50/60 Hz maximum) || 1000-1000 V - AC 400 Hz maximum)
[Ithe] Conventional Enclosed Thermal Current
8 A
Earthing System
IT || TT || TN-S
Relay Application
protection relay
Product Or Component Type
residual current protection relay
Range
VigiPacT
Residual Earth-Leakage Time Delay Adjustment Type
instantaneous for 0.03-0.03 A || adjustable 9 settings 0-4.5 s for 0.03-30 A
Residual Earth-Leakage Sensitity Adjustment Type
adjustable 9 settings
Power Consumption In Va
4 VA
[Us] Rated Supply Voltage
220...240 V AC 50/60 Hz 55...110 %
[Uimp] Rated Impulse Withstand Voltage
8 kV
Minimum Load
10 mA 12 V
Device Short Name
RH99P

Modelli CAD

traceparts
traceparts
Scaricare