- Network Frequency
- 60 Hz || 50 Hz
- Communication Port Support
- screw terminal block RS485
- Output Voltage
- 5...40 V DC@50 mA
- Sampling Rate
- 32 samples/cycle
- Number Of Outputs
- 1 digital (static)
- Mounting Support
- DIN rail
- Maximum Value Measured
- 99999999.9 kWh || 99999999 MWh
- Standards
- BS EN 61326-1 || IEC 61326-1 || EN 61326-1 || BS EN 61010-1:2010 || EN 61010-1:2010 || IEC 61010-1:2010 || UL 61010-1:2010 || BS EN 61010-2-30 || IEC 61010-2-30 || EN 61010-2-30 || UL 61010-2-30 || ANSI C12.20
- Type Of Measurement
- active and reactive energy || active and reactive power || current || voltage
- Communication Port Protocol
- Modbus RTU 9.6, 19.2 and 38.4 kbauds even/odd or none
- Product Certifications
- CE IEC 61010-1 safety) || CE EN 61557-12 power monitor) || CE EN/IEC 61326-1 EMC) || UKCA BS EN 61010-1 safety) || UKCA BS EN 61557-12 power monitor) || UKCA BS EN 61326-1 EMC) || cULus UL 61010-1 safety) || cULus EN 61010-1 safety) || KZ || RCM
- Number Of Inputs
- 1 digital 0...5 V/11...40 V 24 V DC
- Measurement Current
- 1-32767000 mA
- Wire Stripping Length
- input/output circuit: 6 mm || voltage circuit: 8 mm || current circuit: 8 mm || communication: 7 mm
- Connections - Terminals
- current circuit screw terminals 6-6 mm² || voltage circuit screw terminals 2.5-2.5 mm² || input/output circuit screw terminals 1.5-1.5 mm² || communication screw terminals 2.5-2.5 mm²
- Information Displayed
- tariff 4)
- Mounting Mode
- clip-on
- Local Signalling
- Green indicator light power ON || Yellow flashing LED accuracy checking || alarm overload || Yellow indicator light communications are active on the Modbus port (Modbus)
- Technology Type
- electronic
- Poles Description
- 3P + N || 1P + N || 3P
- Analogue Input Type
- split core current transducer 0.333 V or 1 V
- Display Type
- LCD display
- Tightening Torque
- input/output circuit 0.5-0.5 N.m Philips || voltage circuit 0.5-0.5 N.m Philips || current circuit 0.8-0.8 N.m pozidriv || communication 0.5-0.5 N.m Philips
- Device Application
- sub billing || multi-tariff || partial meter
- Metering Type
- active, reactive, apparent energy (signed, four quadrant)
- Accuracy Class
- class 0.5S active energy IEC 62053-22 || class 0.5S active energy ANSI C12.20
- Rated Voltage
- 100-277 V +/- 20 % || 173-480 V +/- 20 %