Un totale di 11 Parts In-Stock da 16 Distributors

Additional Information

Part Number
LC1SK0600M7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Ambient Air Temperature For Operation
-20-50 °C
Height
56 mm
Net Weight
0.132 kg
Ambient Air Temperature For Storage
-50-70 °C
Protective Treatment
TC IEC 60068 || TC DIN 50015
Ip Degree Of Protection
IP2X VDE 0106
Operating Altitude
6561.68 ft (2000 m) without derating
Width
27 mm
Depth
55.5 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1503003EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1503003EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Product Certifications
CB Scheme || CE || UKCA || EAC || cULus
[Uc] Control Circuit Voltage
220 V AC 50/60 Hz
Average Impedance
4 mOhm - Ith 12 A 50 Hz
Control Circuit Voltage Limits
operational: 0.85...1.1 Uc (at <50 °C) || drop-out: 0.2...0.75 Uc (at <50 °C)
[Ith] Conventional Free Air Thermal Current
12 A (at 55 °C) for power circuit
Standards
EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Mounting Support
rail
Control Circuit Type
AC 50/60 Hz
Rated Breaking Capacity
52 A at <= 400 V for power circuit conforming to NF C 63-110 || 52 A at <= 400 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
66 A at 690 V AC conforming to IEC 60947 || 66 A at 690 V AC conforming to NF C 63-110
Associated Fuse Rating
16 A gI at <= 440 V for power circuit conforming to IEC 60947
Inrush Power In Va
16-16 VA (at 20 °C)
Connections - Terminals
power circuit connector 1 0.35-6 mm²flexible with cable end || power circuit connector 1 0.5-6 mm²flexible without cable end || power circuit connector 1 1.5-6 mm²solid || power circuit connector 2 0.35-1.5 mm²flexible with cable end || power circuit connector 2 0.35-2.5 mm²flexible without cable end || power circuit connector 2 1.5-4 mm²solid
Maximum Operating Rate
1200 cyc/h
Tightening Torque
0.8 N.m connector pozidriv No 1
Mechanical Durability
10 Mcycles
Hold-In Power Consumption In Va
4.2-4.2 VA (at 20 °C)
Operating Time
6...8 ms coil de-energisation and NO opening || 7...14 ms coil energisation and NO closing
[Ui] Rated Insulation Voltage
690 V IEC 60947 || 690 V VDE 0110 group C || 690 V BS 5424 || 690 V UL 508 || 690 V CSA C22.2 No 14
[Icw] Rated Short-Time Withstand Current
50 A 55 °C for power circuit
Heat Dissipation
1.4-1.4 W 50/60 Hz

Specifications

[Ue] Rated Operational Voltage
power circuit 690 V AC 50/60 Hz
Contactor Application
motor control || resistive load
Product Or Component Type
mini contactor
Product Name
TeSys SK
Range
TeSys
Pole Contact Composition
2 NO
Utilisation Category
AC-1 || AC-3
[Ie] Rated Operational Current
6 A at <= 440 V AC AC-3 || 12 A (at <55 °C) AC AC-1
Poles Description
2P
Device Short Name
LC1SK

Documenti

Data Sheet

Scaricare

Modelli CAD

Parti in traccia
Parti in traccia
Scaricare

Prodotti correlati