TeSys Deca reversing contactor - 3P - <= 440 V - 9 A AC-3 - 24...60 V AC/DC coil
LC2D09BNE
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 113 Parts In-Stock da 19 Distributors

Additional Information

Part Number
LC2D09BNE
UNSPSC
39121529
Tariff Code
8536490080
Country of Origin
FR

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
77 mm
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Net Weight
0.783 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Color
Gray SE GREY 6) || Green SE GREEN 2)
Width
90 mm
Depth
86 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1609001EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1609001EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts & cables product

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Control Circuit Voltage Limits
<= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC || 0.8...1.1 Uc -40-60 °C operational DC || 1...1.1 Uc 60-70 °C operational AC/DC
Hold-In Power Consumption In W
0.6-0.6 W 20 °C
Insulation Resistance
> 10 MOhm for signalling circuit
Inrush Power In Va
15-15 VA 50/60 Hz 20 °C)
Coil Technology
built-in bidirectional peak limiting
Minimum Switching Voltage
17 V for signalling circuit
Signalling Circuit Frequency
25...400 Hz
Heat Dissipation
0.6-0.6 W 50/60 Hz
Inrush Power In W
14-14 W 20 °C
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
0.9-0.9 VA 20 °C) 50/60 Hz

Specifications

Interlocking Type
mechanical
[Uc] Control Circuit Voltage
24...60 V AC 50/60 Hz || 24...60 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Power Dissipation Per Pole
1.56 W AC-1 || 0.2 W AC-3 || 0.2 W AC-3e
Average Impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 25 A (at 60 °C) for power circuit
Mounting Support
rail || plate
Control Circuit Type
AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
motor control || resistive load
Rated Breaking Capacity
250 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type
reversing contactor
Product Certifications
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Irms Rated Making Capacity
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
Product Name
Tesys Deca green || TeSys Deca
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Connections - Terminals
power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid || power circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid
Range
TeSys || TeSys Deca
Pole Contact Composition
3 NO
Device Presentation
preassembled with reversing power busbar
Utilisation Category
AC-3 || AC-1 || AC-3e
[Ie] Rated Operational Current
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
Operating Time
45...55 ms closing || 20...90 ms opening
Maximum Operating Rate
3600 cyc/h 60 °C
Electrical Durability
2.4 Mcycles 8 A AC-3 <= 440 V || 0.6 Mcycles 25 A AC-1 <= 440 V || 2.4 Mcycles 8 A AC-3e <= 440 V
Tightening Torque
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Poles Description
3P
Overvoltage Category
III
Motor Power Kw
2.2 kW at 220...230 V AC 50 Hz || 4 kW at 380...400 V AC 50 Hz || 4 kW at 415 V AC 50 Hz || 4 kW at 440 V AC 50 Hz || 5.5 kW at 500 V AC 50 Hz || 5.5 kW at 660...690 V AC 50 Hz
Maximum Horse Power Rating
0.33 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
Mechanical Durability
15 Mcycles
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
105 A 40 °C - 10 s for power circuit || 210 A 40 °C - 1 s for power circuit || 30 A 40 °C - 10 min for power circuit || 61 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover
with

Documenti

Data Sheet

Scaricare

Modelli CAD

Parti in traccia
Parti in traccia
Scaricare

Prodotti correlati