Schneider Electric
LV430403
1 / 2
Descrizione
This is a 3 poles basic frame for Compact NSX160F. Compact NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 36kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 105mm x 161mm x 86mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX160F is part of Schneider Electric EcoStruxure Power architecture.- Country of Origin
- PL
- Part Number
- LV430403
- Tariff Code
- 85362090
- EAN
- 3606480006593
- UNSPSC
- 39121601
€116.10
net€129.00
Spedizione da:
€25.00
1
Metodi di pagamento:
- Migliore offerta da:
- Fornitore Automa.Net di fiducia
- Disponibilità:
- 1 pz.DisponibileAggiornato il: 09-11-2024
- Garanzia:
- 24 mesi
- Consegna stimata:
- 15-18 novembre a Regno Unito
- Condizione:
- Usato
Usato - Un articolo usato in precedenza con possibili segni di usura estetica. È completamente operativo e funziona come previsto, anche se l'imballaggio originale potrebbe mancare.
Informazioni sulla spedizione
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia
Specifications
- Network Frequency
- 50/60 Hz
- Line Rated Current
- 160 A 40 °C
- Range Of Product
- ComPact NSX100...250
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Network Type
- AC
- Product Or Component Type
- basic frame
- Range
- ComPact
- Control Type
- toggle
- Utilisation Category
- category A
- Mounting Mode
- fixed
- Breaking Capacity
- 10 kA 600 V AC 50/60 Hz UL 508 || 85 kA 240 V AC 50/60 Hz UL 508 || 22 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 35 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 36 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 8 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 || 85 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 480 V AC 50/60 Hz UL 508 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes EN/IEC 60947-2
- Poles Description
- 3P
- Device Application
- distribution
- Device Short Name
- NSX160F
- Circuit Breaker Name
- Compact NSX160F
Contractual warranty
- Warranty
- 18 months
Complementary
- [Ics] Rated Service Breaking Capacity
- 35 kA 440 V AC 50/60 Hz IEC 60947-2 || 36 kA 380/415 V AC 50/60 Hz IEC 60947-2 || 85 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 22 kA 525 V AC 50/60 Hz IEC 60947-2 || 30 kA 500 V AC 50/60 Hz IEC 60947-2 || 8 kA 660/690 V AC 50/60 Hz IEC 60947-2
- Height
- 161 mm
- Connection Pitch
- 35 mm
- Mounting Support
- backplate
- Downside Connection
- front
- Upside Connection
- front
- Electrical Durability
- 40000 cycles 440 V AC 50/60 Hz In/2 IEC 60947-2 || 15000 cycles 690 V AC 50/60 Hz In/2 IEC 60947-2 || 20000 cycles 440 V AC 50/60 Hz In IEC 60947-2 || 7500 cycles 690 V AC 50/60 Hz In IEC 60947-2
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz IEC 60947-2
- Mechanical Durability
- 40000 cycles IEC 60947-2
- Protection Type
- without protection
- [Uimp] Rated Impulse Withstand Voltage
- 8 kVIEC 60947-2
- Width
- 105 mm
- Depth
- 86 mm
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- UL || CSA
- Ik Degree Of Protection
- IK07 IEC 62262
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- EN/IEC 60947-2 || UL 508
- Ip Degree Of Protection
- IP40 conforming to IEC 60529
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -50-85 °C
Modelli CAD
traceparts
Scaricare