power meter PowerLogic PM5330, modbus, up to 31st Harmonic, 256KB 2DI/2DO 35 alarms
METSEPM5330
METSEPM5330
METSEPM5330
METSEPM5330
METSEPM5330
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
€204.00
1
Metodi di pagamento:
Un totale di 20 Parts In-Stock da 25 Distributors

Additional Information

Part Number
METSEPM5330
UNSPSC
39121106
Tariff Code
9030390100
Country of Origin
IN

Environment

Ambient Air Temperature For Operation
-25-70 °C meter
Electromagnetic Compatibility
conducted and radiated emissions class B conforming to EN 55022 || immunity to conducted disturbances - test level: 150 kHz...80 MHz level 4 conforming to IEC 61000-4-6 || electrical fast transient/burst immunity test level 3 conforming to IEC 61000-4-4 || radiated radio-frequency electromagnetic field immunity test level 4 conforming to IEC 61000-4-3 || voltage dips and interruptions immunity test class B conforming to IEC 61000-4-11 || limits for harmonic current emissions class A conforming to IEC 61000-3-2 || electrostatic discharge level 4 conforming to IEC 61000-4-2 || conducted RF disturbances level 3 conforming to IEC 61000-4-6 || magnetic field at power frequency level 4 conforming to IEC 61000-4-8 || immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || voltage dips and interruptions immunity test conforming to IEC 61000-4-11 || limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 || electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
Pollution Degree
2
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
5-95 % 50-50 °C non-condensing
Ip Degree Of Protection
display IP54 IEC 60529 || rear IP30 IEC 60529
Operating Altitude
6561.68 ft (2000 m) CAT III || 9842.52 ft (3000 m) CAT II

Complementary

Network Frequency
50 Hz || 60 Hz
Communication Port Support
RS485
Power Quality Analysis
up to the 31st harmonic
Height
96 mm
Measurement Voltage
35-760 V AC 45...65 Hz between phases || 20-400 V AC 45...65 Hz between phase and neutral
Sampling Rate
64 samples/cycle
Memory Capacity
256 kB
Number Of Outputs
2 relay || 2 digital
Standards
UL 61010-1 || IEC 62053-22:2020 || IEC 61557-12:2015 || EN 50470-3 || IEC 60529 || IEC 62053-24 || EN 50470-1 || IEC 62053-23:2020 || IEC 62052-11:2020 || IEC 62052-31:2015
Product Certifications
CE IEC 61010-1 || cULus UL 61010-1
Type Of Measurement
current || voltage || frequency || power factor || energy || active and reactive power
Communication Port Protocol
Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V || JBUS
Frequency Measurement Range
45-65 Hz
Ride-Through Time
80 ms 120 V AC typical || 100 ms 230 V AC typical || 100 ms 415 V AC typical || 50 ms 125 V DC typical
Display Resolution
128 x 128 pixels
Number Of Inputs
2 digital
Net Weight
430 g
Depth
72 mm
Measurement Current
5-8500 mA
Connections - Terminals
voltage circuit screw terminal block4 || control circuit screw terminal block2 || current transformer screw terminal block6 || input/output circuit screw terminal block6 || relay output screw terminal block4 || Ethernet network RJ45 connector
Information Displayed
tariff 4)
[Us] Rated Supply Voltage
90...450 V AC 45...65 Hz || 100...300 V DC
Mounting Mode
flush-mounted
Measurement Accuracy
active energy +/- 0.5 % || reactive energy +/- 2 % || active power +/- 0.5 % || apparent power +/- 0.5 % || frequency +/- 0.05 % || power factor +/- 0.5 || current +/- 0.5 % || voltage +/- 0.5 % || apparent energy +/- 0.5 % || reactive power +/- 2 %
Mounting Support
framework
Poles Description
3P + N || 3P || 1P + N
Data Recording
maintenance logs || time stamping || alarm logs || data logs || min/max of instantaneous values || event logs
Line Rated Current
1 A || 5 A
Analogue Input Type
voltage (impedance 5 MOhm) || current (impedance <= 0.3 mOhm)
Width
96 mm
Display Type
monochrome graphic LCD
Device Application
power monitoring || multi-tariff
Accuracy Class
class 0.5S active energy IEC 62053-22
Maximum Power Consumption In Va
11 VA 415 V

Specifications

Product Or Component Type
power meter
Product Name
PowerLogic PM5000
Range
PowerLogic
Device Short Name
PM5330

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1305025
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1305025
Eu Rohs Directive
Compliant with Exemptions