Wago

787-1606

EPSITRON® CLASSIC power supply; single-phase; output voltage 24 VDC; 2 A
787-1606
  • Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
  • Sconti sulla rivendita fino al 40%!
Registrati
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 1 Part In-Stock da 10 Distributors
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€61.82

Additional Information

Part Number
787-1606
UPC
4055143060431
Tariff Code
85044082900
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : DC-power supply
Class Code : EC002540
Version : 7

Safety And Protection

Isolation voltage (pri.-sec.)
DC 4.242 kV
Protection class
II
Protection type
IP20; per EN 60529
Resistance to reverse feed
≤ DC 35 V
Overvoltage category
II
Pollution degree
2
Transient suppression (primary)
Varistor
Overvoltage protection; secondary
Internal protective circuit || ≤ 37 VDC (in the event of a fault)
Short-circuit-protected
Yes
Open-circuit-proof
Yes
Parallel operation
Yes
Series operation
Yes
MTBF
> 500,000 h (per IEC 61709)

Environmental Requirements

Ambient temperature (operation)
-25 … +70 °C (Device starts at −40 °C (type-tested))
Ambient temperature (storage)
-25 … +85 °C
Relative humidity
5 … 96 % (no condensation permissible)
Derating
-3 %/K (> 50 °C)

Connection Data

Connection type 1
Input/output/signaling
Connection technology
CAGE CLAMP®
WAGO connector
WAGO 721 Series
Solid conductor
0.08 … 2.5 mm² / 28 … 12 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 12 AWG
Strip length
8 … 9 mm / 0.31 … 0.35 inches

Signaling And Communication

Signaling
1 x LED DC OK (green) || 1 x Active signal output DC OK (24 VDC; 20 mA)
Operation status indicator
Green LED (Uo)

Physical Data

Width
45 mm / 1.772 inches
Height
90 mm / 3.543 inches
Depth from upper-edge of DIN-rail
107.5 mm / 4.232 inches

Material Data

Fire load
0.000 MJ
Weight
210.000 g

Input

Phases
1
Nominal input voltage Ui nom
1 x AC 100 … 240 V
Input voltage range
1 x AC 85 … 264 V; DC 120 … 300 V
Input voltage derating
-2.5 %/V (< 95 VAC)
Nominal mains frequency range
44 … 66 Hz; 0 Hz
Input current Ii
≤ 0.48 A (240 VAC); ≤ 0.82 A (100 VAC)
Discharge current
≤ 0.25 mA
Inrush current
≤ 30 A
Power factor correction (PFC)
Passive
Mains failure hold-up time
≥ 120 ms (230 VAC); ≥ 20 ms (100 VAC)

Output

Nominal output voltage Uo nom
DC 24 V (SELV)
Output voltage range
DC 23 … 28.5 V (adjustable)
Default setting
DC 24 V
Nominal output current Io nom
2 A (24 VDC); 2.2 A (< 40 °C)
Nominal output power
48 W
Deviation
≤ 1 %
Residual ripple
≤ 20 mV (peak-to-peak)
Current limitation
1.1 x Io nom (typ.)
Overload behavior
Constant current

Standards And Specifications

Conformity marking
CE
Standards/specifications
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || EN 60335-1 || UL 60950-1 || UL 508 || DNV || SEMI F47

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0006

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4055143060431
Customs tariff number
85044083900

Efficiency/Power Losses

Power loss Pl
≤ 1 W; ≤ 6 W (230 VAC; nominal load)
Power loss (max.) Pl (max.)
7 W (100 VAC / 24 VDC; 2 A)
Efficiency (typ.)
89 %

<B>Circuit Protection</B>

Internal fuse
T 4 A / 250 VAC
Backup fusing (required)
An external DC fuse is required for the DC input voltage.
Backup fusing (recommended)
Circuit breaker: 6 A, 10 A, 16 A; Tripping characteristic: B or C