Square D
LC1K0610B72
1 / 1
- Part Number
- LC1K0610B72
- UPC
- 785901487555
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Main
- Commercial Status
- Commercialised
- Range of product
- TeSys K
- Product or component type
- Contactor
- Device short name
- LC1K
- Contactor application
- Motor control
- Utilisation category
- AC-3
- Utilisation category
- AC-4
- Poles description
- 3P
- Pole contact composition
- 3 NO
- [Ue] rated operational voltage
- 690 V AC 50/60 Hz for power circuit
- [Ie] rated operational current
- 6 A at
- Motor power kW
- 3 kW at 660...690 V AC 50/60 Hz
- Motor power kW
- 3 kW at 500...600 V AC 50/60 Hz
- Motor power kW
- 3 kW at 480 V AC 50/60 Hz
- Motor power kW
- 3 kW at 440 V AC 50/60 Hz
- Motor power kW
- 2.2 kW at 380...415 V AC 50/60 Hz
- Motor power kW
- 1.5 kW at 220...230 V AC 50/60 Hz
- Control circuit type
- AC 50/60 Hz
- Control circuit voltage
- 24 V AC 50/60 Hz
- Auxiliary contact composition
- 1 NO
- [Uimp] rated impulse withstand voltage
- 8 kV
- Overvoltage category
- III
- [Ith] conventional free air thermal current
- 10 A at 20 A at
- Irms rated making capacity
- 110 A AC for signalling circuit conforming to IEC 60947
- Irms rated making capacity
- 110 A AC for power circuit conforming to IEC 60947
- Irms rated making capacity
- 110 A AC for power circuit conforming to NF C 63-110
- Rated breaking capacity
- 70 A at 660...690 V conforming to IEC 60947
- Rated breaking capacity
- 110 A at 380...400 V conforming to IEC 60947
- Rated breaking capacity
- 110 A at 220...230 V conforming to IEC 60947
- Rated breaking capacity
- 80 A at 500 V conforming to IEC 60947
- Rated breaking capacity
- 110 A at 440 V conforming to IEC 60947
- Rated breaking capacity
- 110 A at 415 V conforming to IEC 60947
- [Icw] rated short-time withstand current
- 20 A = 15 s power circuit
- [Icw] rated short-time withstand current
- 110 A 100 ms signalling circuit
- [Icw] rated short-time withstand current
- 90 A 500 ms signalling circuit
- [Icw] rated short-time withstand current
- 80 A 1 s signalling circuit
- [Icw] rated short-time withstand current
- 40 A 45 A 60 A 80 A 85 A 90 A
- Associated fuse rating
- 10 A gG for signalling circuit conforming to VDE 0660
- Associated fuse rating
- 10 A gG for signalling circuit conforming to IEC 60947
- Associated fuse rating
- 25 A aM for power circuit
- Associated fuse rating
- 25 A gG at
- Average impedance
- 3 mOhm at 50 Hz - Ith 20 A for power circuit
- [Ui] rated insulation voltage
- 600 V for signalling circuit conforming to CSA C22.2 No 14
- [Ui] rated insulation voltage
- 600 V for power circuit conforming to CSA C22.2 No 14
- [Ui] rated insulation voltage
- 600 V for signalling circuit conforming to UL 508
- [Ui] rated insulation voltage
- 690 V for signalling circuit conforming to IEC 60947-5-1
- [Ui] rated insulation voltage
- 690 V for signalling circuit conforming to IEC 60947-4-1
- [Ui] rated insulation voltage
- 690 V for power circuit conforming to IEC 60947-4-1
- [Ui] rated insulation voltage
- 600 V for power circuit conforming to UL 508
- Electrical durability
- 1.3 Mcycles 6 A AC-3 at Ue
- Mounting support
- Plate
- Mounting support
- Rail
- Standards
- BS 5424
- Standards
- IEC 60947
- Standards
- NF C 63-110
- Standards
- VDE 0660
- Product certifications
- CSA
- Product certifications
- UL
- Connections - terminals
- Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness: flexible - with cable end
- Connections - terminals
- Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
- Connections - terminals
- Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
- Connections - terminals
- Screw clamp terminals 1 cable(s) 0...0 in² (0.34...2.5 mm²) - cable stiffness: flexible - with cable end
- Connections - terminals
- Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness: flexible - without cable end
- Connections - terminals
- Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
- Tightening torque
- 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
- Tightening torque
- 11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
- Operating time
- 10...20 ms coil energisation and NO closing
- Operating time
- 10...20 ms coil de-energisation and NO opening
- Safety reliability level
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
- Safety reliability level
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- Mechanical durability
- 10 Mcycles
- Operating rate
- 3600 cyc/h
Complementary
- Coil technology
- Built-in bidirectional peak limiting diode suppressor
- Control circuit voltage limits
- 0.2...0.75 Uc at 0.8...1.15 Uc at
- Inrush power in VA
- 30 VA at 68 °F (20 °C)
- Hold-in power consumption in VA
- 4.5 VA at 68 °F (20 °C)
- Heat dissipation
- 1.3 W
- Auxiliary contacts type
- Type instantaneous (1 NO)
- Minimum switching current
- 5 mA for signalling circuit
- Minimum switching voltage
- 17 V for signalling circuit
- Non overlap distance
- 0.02 in (0.5 mm)
- Insulation resistance
- > 10 MOhm for signalling circuit
Environment
- IP degree of protection
- IP2x conforming to VDE 0106
- Protective treatment
- TC conforming to DIN 50016
- Protective treatment
- TC conforming to IEC 60068
- Ambient air temperature for operation
- -13...122 °F (-25...50 °C)
- Ambient air temperature for storage
- -58...176 °F (-50...80 °C)
- Operating altitude
- 6561.68 ft (2000 m) without derating in temperature
- Flame retardance
- Requirement 2 conforming to NF F 16-102
- Flame retardance
- Requirement 2 conforming to NF F 16-101
- Flame retardance
- V1 conforming to UL 94
- Mechanical robustness
- Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
- Mechanical robustness
- Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
- Mechanical robustness
- Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
- Mechanical robustness
- Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
- Mechanical robustness
- Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
- Mechanical robustness
- Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
- Mechanical robustness
- Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
- Mechanical robustness
- Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
- Height
- 2.28 in (58 mm)
- Width
- 1.77 in (45 mm)
- Depth
- 2.24 in (57 mm)
- Product weight
- 0.4 lb(US) (0.18 kg)
Ordering and Shipping Details
- Category
- 22326 - CTR,K-LINE,AC,OPEN,NONREV
- Discount Schedule
- I12
- GTIN
- 00785901487555
- Nbr. of units in pkg.
- 1
- Package weight(Lbs)
- 0.40
- Product availability
- Non-Stock - Not normally stocked in distribution facility
- Returnability
- N
- Country of origin
- FR
Offer Sustainability
- Sustainable offer status
- Green Premium product
- RoHS
- Compliant - since 0825 -
- RoHS
- Schneider Electric declaration of conformity
- REACh
- Reference not containing SVHC above the threshold
- Product environmental profile
- Available
- Product environmental profile
- Download Product environmental
- Product end of life instructions
- Need no specific recycling operations
Contractual Warranty
- Period
- 18 months
Dokumenty
Data Sheet
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne