- Rated Operational Current AC-21A (Ie)
- (380 ... 415 V) 125 A(500 V) 125 A(690 V) 125 A
- Rated Operational Current AC-22A (Ie)
- (380 ... 415 V) 125 A(500 V) 125 A(690 V) 125 A
- Rated Operational Current AC-23A (Ie)
- (380 ... 415 V) 90 A(500 V) 70 A(690 V) 50 A
- Rated Operational Power AC-23A (Pe)
- (220 ... 240 V) 22 kW(400 ... 415 V) 45 kW(500 V) 45 kW(690 V) 45 kW
- Conventional Free-air Thermal Current (Ith)
- Θ = 40 °C 125 A
- Conventional Thermal Current (Ithe)
- Fully Enclosed 125 A
- Rated Impulse Withstand Voltage (Uimp)
- 8 kV
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 750 V
- Rated Operational Voltage
- Main Circuit 750 V
- Rated Short-Circuit Making Capacity (Icm)
- (690 V) 3.6 kA
- Rated Short-time Withstand Current Low Voltage (Icw)
- for 1 s 2.5 kA
- Rated Conditional Short-Circuit Current (Inc)
- (125 A fuse, 415 V) 50 kA(125 A fuse, 690 V) 10 kA(63 A fuse, 690 V) 50 kA
- Power Loss
- at Rated Operating Conditions per Pole 6.3 W
- Pollution Degree
- 3
- Handle Type
- Handle and shaft not included
- Fourth Pole Position
- Right Side
- Fourth Pole Type
- Switched - Simultaneous Function
- Switches Operating Mechanism
- Mechanism on Top of the Switch
- Distance Between Phases
- Standard
- Position of Line Terminals
- Top In - Bottom OutBottom In - Top Out
- Operating Mode
- Front operated
- Standards
- IEC 60947-3
- Special Functions
- No
- Mounting Type
- Door mounting
- Number of Poles
- 4
- Cable Cross-Section
- Cu 10 ... 70 mm²
- Degree of Protection
- Front IP20
- Terminal Type
- Screw Terminals
- Tightening Torque
- acc. IEC 60947-1 6 N·m
- Mechanical Durability
- 20000
- Lock Type
- No