Schmersal

101181911

1 / 3
thumbnail
thumbnail
thumbnail
Part Number
101181911
ETIM
Group Code : EG000019
Group Description : Relays
Class Description : Device for monitoring of safety-related circuits
Class Code : EC001449
Version : 7
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Electrical data - Relay outputs (auxiliary contacts)

Switching capacity, maximum
24 VDC
Switching capacity, maximum
2 A

Electrical data

Frequency range
50 Hz | 60 Hz
Operating voltage
24 VAC -15 % / +10 % | 24 VDC -10 % / +20 %
Ripple voltage
10 %
Rated operating voltage
24 VAC
Rated operating voltage
24 VDC
Rated AC voltage for controls, 50 Hz, minimum
20.4 VAC
Rated control voltage at AC 50 Hz, maximum
26.4 VAC
Rated AC voltage for controls, 60 Hz, minimum
20.4 VAC
Rated control voltage at AC 60 Hz, maximum
26.4 VAC
Rated AC voltage for controls at DC minimum
20.4 VDC
Rated control voltage at DC, maximum
28.8 VDC
Electrical power consumption
1.5 W
Electrical power consumption
3 VA
Contact resistance, maximum
0.1 Ω
Note (Contact resistance)
in new state
Drop-out delay in case of power failure, typically
80 ms
Drop-out delay in case of emergency, typically
20 ms
Pull-in delay at automatic start, maximum, typically
100 ms
ON delay at automatic start
Adjustable
Pull-in delay at RESET, typically
20 ms
Material of the contacts, electrical
AgSn0. self-cleaning, positive drive

Note

Note (General)
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.

Mechanical data - Dimensions

Width
22.5 mm
Height
100 mm
Depth
121 mm

Ambient conditions - Insulation values

Rated impulse withstand voltage U
4 kV
Overvoltage category
III
Degree of pollution
2

General data - Features

Stop-Category
0
Electronic Fuse
Yes
Wire breakage detection
Yes
Cross-circuit detection
Yes
Start input
Yes
Feedback circuit
Yes
Reset edge detection
Yes
Earth connection detection
Yes
Integral system diagnostics, status
Yes
Number of LEDs
3
Number of normally closed (NC)
2
Number of safety contacts
2

General data

Standards
EN IEC 62061 | EN ISO 13849-1 | EN IEC 60947-5-1 | EN IEC 60947-5-3 | EN IEC 60947-5-5 | EN IEC 61508 | EN IEC 60204-1 | EN IEC 60947-1
Climatic stress
EN 60068-2-78
Enclosure material
Glass-fibre reinforced thermoplastic, ventilated
Gross weight
230 g

Safety classification

Standards
EN IEC 60947-5-1 | EN IEC 61508
Performance Level, stop 0, up to
e
Category, Stop 0
4
Diagnostic Coverage (DC) Level, Stop 0
≥ 99 %
PFH value, Stop 0
2.00 x 10⁻⁸ /h
Safety Integrity Level (SIL), Stop 0, suitable for applications in
3
Mission time
20 Year(s)
Common Cause Failure (CCF), minimum
65

Wiring example

Note (Wiring diagram)
The wiring diagram is shown with guard doors closed and in de-energised condition. | If only one external relay or contactor is used to switch the load, the system can be classified in Control Category 3 to ISO 13849-1, if exclusion of the fault “Failure of the external contactor” can be substantiated and is documented, e.g. by using a reliable down-rated contactor. A second contactor leads to an increase in the level of security by redundant switching to switch the load off. | To secure a guard door up to PL e and Category 4 | The feedback circuit monitors the positions of the positive-guided NC contacts on the conactors Ka and Kb.

Other data

Note (applications)
Guard system | Emergency-Stop button | Pull-wire emergency stop switches

Ambient conditions

Degree of protection of the enclosure
IP40
Degree of protection of the mounting space
IP54
Degree of protection of clips or terminals
IP20
Ambient temperature
-25 ... +60 °C
Storage and transport temperature, minimum
-40 °C
Storage and transport temperature, maximum
+85 °C
Resistance to vibrations
10 ... 55 Hz, Amplitude 0.35 mm
Restistance to shock
30 g / 11 ms

Mechanical data - Connection technique

Termination
rigid or flexible | Screw terminals M20 x 1.5
Terminal designations
IEC/EN 60947-1
Cable section, minimum
0.25 mm²
Cable section, maximum
2.5 mm²
Tightening torque of Clips
0.6 Nm

Electrical data - Safe relay outputs

Voltage, Utilisation category AC-15
250 VAC
Current, Utilisation category AC-15
6 A
Voltage, Utilisation category DC-13
24 VDC
Current, Utilisation category DC-13
6 A
Switching capacity, minimum
10 VDC
Switching capacity, minimum
10 mA
Switching capacity, maximum
250 VAC
Switching capacity, maximum
8 A

Mechanical data

Mechanical life, minimum
10,000,000 Operations
Mounting
Snaps onto standard DIN rail to EN 60715

Specifications

Width
22.5 mm
Height
100 mm
Depth
121 mm

Approvals - Standards

Certificates
cULus | CCC

Electrical data - Electromagnetic compatibility (EMC)

EMC rating
EMC-Directive

Electrical data - Digital inputs

Conduction resistance, maximum
40 Ω

Status indication

Indicated operating states
Position relay K2 | Position relay K1