- Power Dissipation Per Pole
- 12.5 W AC-1
- Average Impedance
- 0.8 mOhm - Ith 125 A 50 Hz for power circuit
- [Ith] Conventional Free Air Thermal Current
- 125 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.3...0.6 Uc -40-70 °C drop-out AC 50 Hz || 0.85...1.1 Uc -40-55 °C operational AC 50 Hz || 1...1.1 Uc 55-70 °C operational AC 50 Hz
- Mounting Support
- rail || plate
- Contact Compatibility
- M1
- Control Circuit Type
- AC 50 Hz
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Rated Breaking Capacity
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 200 A gG at <= 690 V coordination type 1 for power circuit || 160 A gG at <= 690 V coordination type 2 for power circuit
- Inrush Power In Va
- 200-200 VA 50 Hz cos phi 0.75 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Pole Contact Composition
- 4 NO
- Connections - Terminals
- control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 4-50 mm² - cable stiffness: solid without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: solid without cable end
- Coil Technology
- without built-in suppressor module
- Operating Time
- 20...35 ms closing || 6...20 ms opening
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
- Electrical Durability
- 0.8 Mcycles 125 A AC-1 <= 440 V
- Mechanical Durability
- 10 Mcycles
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 20-20 VA 50 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category
- III
- Motor Power Kw
- 22 kW at 220...230 V AC 50/60 Hz || 37 kW at 380...400 V AC 50/60 Hz || 45 kW at 660...690 V AC 50/60 Hz || 55 kW at 500 V AC 50/60 Hz || 45 kW at 415...440 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current
- 640 A 40 °C - 10 s for power circuit || 990 A 40 °C - 1 s for power circuit || 135 A 40 °C - 10 min for power circuit || 320 A 40 °C - 1 min for power circuit
- Heat Dissipation
- 6-10 W at 50 Hz
- Protective Cover
- without