- Product Certifications
- CE || cULus || CCC || UKCA || RCM || EAC || DNV || ABS || BV || CCS
- Device Connection
- in the motor supply line || to the motor delta terminals
- Height
- 290.0 mm
- Standards
- IEC 60947-4-2 || UL 60947-4-2 || IEC 60664-1
- Transmission Frame
- RTU
- Analogue Output Type
- current output AQ1 0...20 mA or 0...10 V 500 Ohm
- [Uc] Control Circuit Voltage
- 110...250 V AC 50/60 Hz - 15...10 %
- Maximum Switching Current
- relay outputs 2 A 250 V AC || relay outputs 2 A 30 V DC || relay outputs
- Relay Output Number
- 3
- Data Format
- 8 bits, configurable odd, even or no parity
- Marking
- CE || CCC || UKCA || EAC || RCM || cULus
- Output Current Drift
- 150-700 %
- Display Screen Available
- true
- Net Weight
- 8.3 kg
- Relay Output Type
- relay outputs R1A 1 NO || relay outputs R1B 1 NO || relay outputs RIC NO/NC programmable
- Connector Type
- 1 RJ45
- Analogue Input Number
- 1
- Communication Data Link
- serial
- Function Available
- external bypass control || pre-heating || smoke extraction || multi-motor cascade || second motor set || user management || ports and services hardening || security event logging || cybersecure firmware update || single direction
- Discrete Output Number
- 2
- Communication Port Protocol
- Modbus serial
- Discrete Input Type
- STOP) logic inputs, 3500 Ohm || RUN) logic inputs, 3500 Ohm || DI3) programmable as logic input, 3500 Ohm || DI4) programmable as logic input, 3500 Ohm
- Minimum Switching Current
- 100 mA 12 V DC relay outputs
- Analogue Output Number
- 1
- Physical Interface
- 2-wire RS 485
- Method Of Access
- slave Modbus serial
- Integrated Motor Overload Protection
- true
- [In] Rated Current Pwr Loss Specifctn
- 88.0 A
- Discrete Input Number
- 4
- Accuracy Class
- class 10E
- Power Loss Per Device Current Dependent
- 270.0 W
- Number Of Addresses
- 0-227 Modbus serial
- Apparent Power
- 0.09 kVA
- Operating Position
- vertical +/- 10 degree
- Power Loss Static Current Independent
- 25.0 W
- Type Of Polarization
- no impedance Modbus serial
- Width
- 190.0 mm
- Transmission Rate
- 1200...256000 bit/s
- Depth
- 247.0 mm
- Discrete Input Logic
- programmable digital input < 5 V
- Protection Type
- phase failure line || integrated thermal protection motor || thermal protection starter || current overload motor || underload motor || excessive starting time, locked rotor motor || motor phase loss motor || line supply phase loss line || line supply phase loss motor || thermal protection motor
- Discrete Output Type
- DQ1) programmable digital output <= 30 V || DQ2) programmable digital output <= 30 V