Schneider Electric
LC1D50E7
IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 48VAC 50/60Hz coil, open
- Ottenete termini di pagamento fino a 90 giorni da 500+ fornitori.
- Sconti sulla rivendita fino al 40%!
Invia una richiesta di prezzo
1
Metodi di pagamento:
Un totale di 1 Part In-Stock da 9 Distributors
Condizioni del prodotto:
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
Invia una richiesta di prezzo
Additional Information
- Part Number
- LC1D50E7
- UNSPSC
- 39121529
- Tariff Code
- 8536490065
- Country of Origin
- CZ
Environment
- Product Certifications
- CCC || BV || CSA || GOST || UL || DNV || GL || LROS (Lloyds register of shipping) || UKCA
- Height
- 127 mm
- Standards
- UL 508 || IEC 60947-5-1 || EN 60947-4-1 || EN 60947-5-1 || CSA C22.2 No 14 || IEC 60947-4-1
- Climatic Withstand
- IACS E10 exposure to damp heat
- Net Weight
- 2.185 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP2X VDE 0106 || IP2X IEC 60529
- Mechanical Robustness
- shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor opened 10 Gn for 11 ms)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 85 mm
- Depth
- 176 mm
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on energisation between NC and NO contacts || 1.5 ms on de-energisation between NC and NO contacts
- Minimum Switching Current
- 5 mA for control circuit
- Power Dissipation Per Pole
- 9.6 W AC-1 || 3.7 W AC-3e || 3.7 W AC-3
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for control circuit
- Control Circuit Voltage Limits
- 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz || 0.75...1.25 Uc -40-60 °C operational DC || 0.1...0.3 Uc -40-70 °C drop-out DC
- Mounting Support
- rail || plate
- Control Circuit Type
- DC standard
- Safety Reliability Level
- B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 || B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
- Hold-In Power Consumption In W
- 7.4-7.4 W 20 °C
- Insulation Resistance
- > 10 MOhm for control circuit
- Rated Breaking Capacity
- 900 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for control circuit conforming to IEC 60947-5-1 || 900 A at 440 V for power circuit conforming to IEC 60947 || 250 A DC for control circuit conforming to IEC 60947-5-1
- Associated Fuse Rating
- 100 A gG at <= 690 V coordination type 1 for power circuit || 100 A gG at <= 690 V coordination type 2 for power circuit conforming to IEC 60947-5-1 || 10 A gG for control circuit conforming to IEC 60947-5-1
- Inrush Power In Va
- 160-160 VA cos phi 0.75 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: rigid || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: rigid without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 34 ms
- Operating Time
- 12...26 ms closing || 50 ms closing || 20 ms opening
- Minimum Switching Voltage
- 17 V for control circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw terminal flat Ø 6 to Ø 8 mm || control circuit 1.7 N.m screw clamp terminal pozidriv No 2 || control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm
- Mechanical Durability
- 10000000 cycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors || 15 hp at 200/208 V AC 60 Hz for 3 phase motors || 15 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 40 hp at 575/600 V AC 60 Hz for 3 phase motors || 3 hp at 115 V AC 60 Hz for 1 phase motors
- Motor Power Kw
- 25 kW at 415 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3) || 30 kW at 500 V AC 50 Hz (AC-3) || 33 kW at 660...690 V AC 50 Hz (AC-3) || 15 kW at 220...230 V AC 50 Hz (AC-3) || 11 kW at 400 V AC 50 Hz (AC-4) || 30 kW at 1000 V AC 50 Hz (AC-3) || 22 kW at 380...400 V AC 50 Hz (AC-3e) || 25 kW at 415 V AC 50 Hz (AC-3e) || 30 kW at 440 V AC 50 Hz (AC-3e) || 30 kW at 500 V AC 50 Hz (AC-3e) || 33 kW at 660...690 V AC 50 Hz (AC-3e) || 15 kW at 220...230 V AC 50 Hz (AC-3e) || 30 kW at 1000 V AC 50 Hz (AC-3e) || 22 kW at 380...400 V AC 50 Hz (AC-3)
- [Ui] Rated Insulation Voltage
- control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL IEC 60947-1 || control circuit 690 V IEC 60947-1 || power circuit 690 V CSA IEC 60947-1 || control circuit 600 V CSA
- Rated Operational Power In W
- 12 W 48 V DC-13 10000000 cycles - control circuit || 38 W 48 V DC-13 3000000 cycles - control circuit
- Protective Cover
- with
Specifications
- [Uc] Control Circuit Voltage
- 48 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Range Of Product
- TeSys Deca
- Contactor Application
- motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-2 || AC-4 || AC-3 || AC-3e
- [Ie] Rated Operational Current
- 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 50 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
- Poles Description
- 3P
- Device Short Name
- LC1D
Documenti
Data Sheet
ScaricareModelli CAD
traceparts
ScaricareAltre categorie
AttuatoriBlocchiCavi, tubi e manichetteCompressoriControlloGiunzioni e raccordiCilindri e PistoniElettronicaFiltriHVACPC industriali e HMIsIlluminazioneTecnica lineareMotoriAlimentatoreTrasmissione di potenzaPompe e ValvoleEnergia rinnovabileRoboticaGuarnizioni, Anelli e ConnettoriSensori e dispositivi di misuraStrumenti e AccessoriCNCAltro