- Number Of Outputs
- 4 on/off configurable pulsed output
- Height
- 100 mm
- Mounting Support
- 35 mm symmetrical DIN rail
- Minimum Output Voltage
- 24 V relay output
- Minimum Output Current
- 20 mA relay output
- [Ith] Conventional Free Air Thermal Current
- 16 A
- Input/Output Type
- semiconductor output 24 V DC, 20 mA Z2, not safety-related || pulsed output for diagnostics 24 V DC, 20 mA Z1, not safety-related
- Associated Fuse Rating
- 10 A gG NO relay output circuit IEC 60947-1
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV II IEC 60947-1
- Net Weight
- 0.350 kg
- Type Of Start
- automatic/manual/monitored
- Number Of Inputs
- 2 positive safety input 24 V DC 8 || 1 negative safety input
- Time Delay Range
- 0...900 s off
- Input Compatibility
- normally closed circuit ISO 14119 || XC limit switch ISO 14119 || mechanical contact ISO 14119 || normally closed circuit ISO 13850 || antivalent pair ISO 14119 || OSSD pair IEC 61496-1-2 || 3-wire proximity sensors PNP
- Power Consumption In Va
- 6.5 VA 24 V AC 50/60 Hz
- [Ie] Rated Operational Current
- 5 A AC-1 for normally open relay contact || 3 A AC-15 for normally open relay contact || 5 A DC-1 for normally open relay contact || 3 A DC-13 for normally open relay contact || 3 A AC-1 for normally closed relay contact || 1 A AC-15 for normally closed relay contact || 3 A DC-1 for normally closed relay contact || 1 A DC-13 for normally closed relay contact
- Auxiliary Contact Composition
- 1 NC configurable || 3 NO configurable || 3 NO immediate
- [Ui] Rated Insulation Voltage
- 250 V 2)IEC 60947-1
- Power Consumption In W
- 3 W 24 V DC
- Maximum Line Resistance
- 500 Ohm
- Input Protection Type
- internal, electronic
- Width
- 45 mm
- Depth
- 120 mm
- Synchronisation Time Between Inputs
- 0.5 s || 2 s || 4 s
- Maximum Response Time On Input Open
- 20 ms