ABB
1SAX121001R1105
EF19-18.9 Electronic Overload Relay 5.7 ... 18.9 A
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€46.94
1
Payment methods:
A total of 1,162 Parts In-Stock from 22 Distributors
Product Conditions:
Offer with manufacturer lead time
Ships in:On Request
Best price:
€48.78
Additional Information
- Part Number
- 1SAX121001R1105
- UNSPSC
- 39122330
- ETIM
- Group Code : EG000017
- Group Description : Low-voltage Industrial Components
- Class Description : Electronic overload relay
- Class Code : EC001080
- Version : 7
Dimensions
- Product Net Width
- 44.4 mm
- Product Net Height
- 85 mm
- Product Net Depth / Length
- 59.3 mm
- Product Net Weight
- 0.158 kg
Technical
- Setting Range
- 5.7 ... 18.9 A
- Rated Operational Voltage
- Auxiliary Circuit 600 V AC/DCMain Circuit 690 V AC
- Rated Operational Current (Ie)
- 18.9 A
- Rated Frequency (f)
- Auxiliary Circuit 50 HzAuxiliary Circuit 60 HzAuxiliary Circuit DCMain Circuit 50 HzMain Circuit 60 Hz
- Rated Impulse Withstand Voltage (Uimp)
- Auxiliary Circuit 6 kVMain Circuit 6 kV
- Rated Insulation Voltage (Ui)
- 690 V
- Number of Poles
- 3
- Number of Auxiliary Contacts NC
- 1
- Number of Auxiliary Contacts NO
- 1
- Number of Protected Poles
- 3
- Conventional Free-air Thermal Current (Ith)
- Auxiliary Circuit NC 6 AAuxiliary Circuit NO 6 A
- Rated Operational Current AC-15 (Ie)
- (240 V) NC 3 A(240 V) NO 3 A(400 V) NC 1.1 A(400 V) NO 1.1 A(500 V) NC 0.75 A(500 V) NO 0.75 A
- Rated Operational Current DC-13 (Ie)
- (125 V) NC 0.55 A(125 V) NO 0.5 A(24 V) NC 1.5 A(24 V) NO 1.5 A(250 V) NC 0.27 A(250 V) NO 0.27 A(60 V) NC 0.55 A(60 V) NO 0.55 A
- Degree of Protection
- IP20
- Pollution Degree
- 3
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
- Connecting Capacity Main Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
- Tightening Torque
- Auxiliary Circuit 0.8 ... 1.2 N·mMain Circuit 0.8 ... 1.5 N·m
- Wire Stripping Length
- Auxiliary Circuit 9 mmMain Circuit 9 mm
- Recommended Screw Driver
- Auxiliary Circuit Pozidriv 2Main Circuit Pozidriv 2
- Mounting Position
- 1 ... 6
- Power Loss
- at Rated Operating Conditions per Pole 0.028 ... 0.304 W
- Suitable For
- AF09AF12AF16AF26
- Standards
- IEC/EN 60947-1IEC/EN 60947-4-1IEC/EN 60947-5-1UL 60947-1UL 60947-4-1
Classifications
- Object Classification Code
- F
- ETIM 4
- EC001080 - Electronic overload relay
- ETIM 5
- EC001080 - Electronic overload relay
- EClass
- V11.0 : 27371502
- IDEA Granular Category Code (IGCC)
- 5365 >> Electronic overload relay
- E-Number (Finland)
- 3706155
- E-Number (Sweden)
- 3224184
Environmental
- Ambient Air Temperature
- Operation -25 ... +70 °COperation Compensated -25 ... +70 °CStorage -50 ... +80 °C
- Ambient Air Temperature Compensation
- Yes
- Maximum Operating Altitude Permissible
- 2000 m
- Resistance to Shock acc. to IEC 60068-2-27
- 11 ms Pulse 25g
- Resistance to Vibrations acc. to IEC 60068-2-6
- 3g / 3 ... 150 Hz
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V AC
- Contact Rating UL/CSA
- (NC:) B600(NC:) Q600(NO:) B600(NO:) Q600
- Connecting Capacity Main Circuit UL/CSA
- Flexible 1/2x 16-10 AWGStranded 1/2x 16-10 AWG
- Connecting Capacity Auxiliary Circuit UL/CSA
- Flexible 1/2x 18-10 AWGStranded 1/2x 18-10 AWG
- Tightening Torque UL/CSA
- Auxiliary Circuit 7 ... 1 in·lbMain Circuit 7 ... 13 in·lb
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900