ABB

1SBL297501R1200

AF38-22-00-12 48-130V50/60HZ-DC Contactor
1SBL297501R1200
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€59.82
1
Payment methods:
A total of 200 Parts In-Stock from 10 Distributors

Dimensions

Product Net Width
45 mm
Product Net Depth / Length
101 mm
Product Net Height
86 mm
Product Net Weight
0.36 kg

Technical

Number of Main Contacts NO
2
Number of Main Contacts NC
2
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 60947-4-1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Control Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 55 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 55 A(690 V) 60 °C 45 A(690 V) 70 °C 37 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 21.2 A(440 V) 60 °C 20 A(500 V) 60 °C 17.6 A(690 V) 60 °C 10.5 A(380 / 400 V) 60 °C 22 A(220 / 230 / 240 V) 60 °C 23.2 A
Rated Operational Power AC-3 (Pe)
(400 V) 11 kW(415 V) 11 kW(440 V) 11 kW(500 V) 11 kW(690 V) 9 kW(220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 1.5 ... 16 mm²Flexible with Insulated Ferrule 1/2x 1.5 ... 16 mm²Rigid Solid 1/2x 1.5 ... 4 mm²Rigid Stranded 1/2x 1.5 ... 16 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Control Circuit 10 mmMain Circuit 12 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type
Screw Terminals

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3705853
E-Number (Sweden)
3211523

Environmental

Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations acc. to IEC 60068-2-6
5 ... 300 Hz 4 g closed position / 2 g open position
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 30 gClosed, Shock Direction: B1 25 gClosed, Shock Direction: B2 15 gClosed, Shock Direction: C1 25 gClosed, Shock Direction: C2 25 gOpen, Shock Direction: A 25 gOpen, Shock Direction: B1 5 gOpen, Shock Direction: B2 10 gOpen, Shock Direction: C1 20 gOpen, Shock Direction: C2 20 g
RoHS Status
Following EU Directive 2011/65/EU

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 55 A
Connecting Capacity Main Circuit UL/CSA
Rigid Solid 1/2x 16-10 AWGRigid Stranded 1/2x 16-6 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWGRigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA
Control Circuit 11 in·lbMain Circuit 22 in·lb

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900