1SDA070912R1

E2.2H 800 Ekip Dip LSI 3p F HR
1SDA070912R1
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Additional Information

Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Number of Poles
3
Power Loss
34 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
800 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 85 kAfor 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA
Rated Uninterrupted Current (Iu)
800 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
CAD Dimensional Drawing
1SDH001252R0083

Dimensions

Product Net Width
276 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
41 kg

ABB EcoSolutions

ABB EcoSolutions
Yes

Eco Transparency

Environmental Product Declaration - EPD
9AKK108468A1902 9AKK108468A1909

Classifications

ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
EClass
V11.1 : 27370409

Environmental

Environmental Information
9AKK10103A1038 9AKK108467A6707
REACH Declaration
9AKK108466A1425
RoHS Information
9AKK108466A1424
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
27884619-f70d-4f9b-895b-78d4a8656e88 Italy (IT)
Simplified SCIP
f4451f04-ca30-497a-809d-0b47dc81fead Hungary (HU)afa2f21e-d149-4a2b-9f9e-2d0ae280ed24 France (FR)31bc8fd1-33b5-446f-a7d8-f21a97ed1cb2 Spain (ES)732d9c57-5d54-4d39-a750-51ffdd5195e0 Belgium (BE)f8f0a3c3-453d-4eef-9d86-bc543b3a6fc9 Bulgaria (BG)8c727513-a9ae-4e25-bfdf-4b249146d45d Croatia (HR)5d4296dd-349e-4950-9cfd-95c216928b3f Germany (DE)6924751d-72ca-4f91-8aeb-10ba67c9240a Estonia (EE)e9706ff3-2b17-472f-af0b-c0d25e2e0b73 Germany (DE)38856696-55c3-46af-8ddc-5c8a7ab0c956 Greece (GR)51a5b9a9-b60f-4411-8d2b-95144d0ebe71 Netherlands (NL)c372523e-1be8-4b6b-aad0-8ef7b047da87 France (FR)32ec3b6c-c237-446f-a298-9e0827da652a Finland (FI)a53814ab-e519-4207-ae73-b57245a8af03 Sweden (SE)cce79621-8991-42f4-a764-81008fbc7f76 Belgium (BE)62abdda5-501c-4622-a2b4-4deaa8167ba9 Denmark (DK)8a2f5c9a-d936-43ab-a1d5-80f6cbdafc8c Germany (DE)7ea56449-5be7-4443-94a2-578ef05ae5c8 Germany (DE)af1bf5a4-6dab-478a-9639-248da85bb1b6 Norway (NO)14ed5481-826f-4a47-b5a9-f0c7c4658e81 Poland (PL)38dd4feb-759d-4294-b384-59f442418a5a Poland (PL)efceb5f4-0a47-470c-8949-c89e77ac6d69 Hungary (HU)4bc8c650-6e4f-416f-994b-f14a5e3b163f Czech Republic (CZ)d1a103aa-821c-4826-b19d-79fb7fae9efe Poland (PL)e416e307-5d04-43b3-a670-98f493cab97b Portugal (PT)8a45a2bd-24fe-4c92-971a-2f32baace96c Sweden (SE)

Circular Value

Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Conflict Minerals Reporting Template (CMRT)
9AKK108467A5658
End of Life Instructions
9AKK108468A2361
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA
9AKK108467A8326

Ordering

Order Code US and Canada
Z2HPEFBB000A000000XX
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090