ABB

1SFL427002R1111

AF116-30-11B-11 Contactor
1SFL427002R1111
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€215.12
1
Payment methods:
A total of 200 Parts In-Stock from 10 Distributors

Dimensions

Product Net Width
90 mm
Product Net Depth / Length
126 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg

Technical

Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 160 A(690 V) 60 °C 145 A(690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 116 A(440 V) 55 °C 116 A(500 V) 55 °C 110 A(690 V) 55 °C 65 A(380 / 400 V) 55 °C 116 A(220 / 230 / 240 V) 55 °C 116
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 116 A(440 V) 60 °C 116 A(500 V) 60 °C 110 A(690 V) 60 °C 65 A(380 / 400 V) 60 °C 116 A(220 / 230 / 240 V) 60 °C 116 A
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW(440 V) 75 kW(500 V) 75 kW(690 V) 55 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW(440 V) 75 kW(500 V) 75 kW(690 V) 55 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Short-Circuit Protective Devices
gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A(220 V) 3 Poles in Series, 40 °C 145 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage DC 210 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main Circuit
Flexible 2 x 10 ... 70 mm²Rigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 1x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars

Eco Transparency

Environmental Product Declaration - EPD
1SFC100092D0201

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706174
E-Number (Norway)
4117616

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value

ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
End of Life Instructions
1SFC100112M0001
Group Waste to Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
Improved Resource Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Sustainable Material Content
Recycled Metal - 37 %

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 160 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 30 hp(208 V AC) Three Phase 30 hp(220 ... 240 V AC) Three Phase 40 hp(440 ... 480 V AC) Three Phase 75 hp(550 ... 600 V AC) Three Phase 100 hp

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900