ABB

1SFL447101R1411

AF140-40-11-14 Contactor
1SFL447101R1411
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€251.30
1
Payment methods:

Dimensions

Product Net Width
120 mm
Product Net Depth / Length
128 mm
Product Net Height
150 mm
Product Net Weight
2.05 kg

Technical

Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 200 A(690 V) 60 °C 175 A(690 V) 70 °C 160 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 140 A(440 V) 55 °C 140 A(380 / 400 V) 55 °C 140 A(220 / 230 / 240 V) 55 °C 140
Rated Operational Power AC-3 (Pe)
(415 V) 75 kW(440 V) 90 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 37 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V
Coil Consumption
Average Pull-in Value 50 Hz 260 V·AAverage Pull-in Value 60 Hz 260 V·AHolding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 205 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 205 V·APull-in at Max. Rated Control Circuit Voltage DC 230 W
Operate Time
Between Coil De-energization and NO Contact Opening 40 ... 70 msBetween Coil Energization and NO Contact Closing 20 ... 55 ms
Connecting Capacity Main Circuit
Flexible 1 x 10 ... 70 mm²Rigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Double Clamp

Eco Transparency

Environmental Product Declaration - EPD
1SFC100092D0201

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706091

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value

ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
End of Life Instructions
1SFC100112M0001
Group Waste to Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
Improved Resource Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Sustainable Material Content
Recycled Metal - 37 %

Technical UL/CSA

NEMA Size
4
Horsepower Rating NEMA
(200 V AC) Three Phase 40 Hp(230 V AC) Three Phase 50 Hp(460 V AC) Three Phase 100 Hp(575 V AC) Three Phase 100 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 200 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 15 Hp(200 V AC) Three Phase 40 hp(208 V AC) Three Phase 40 hp(220 ... 240 V AC) Three Phase 20 Hp(220 ... 240 V AC) Three Phase 50 hp(440 ... 480 V AC) Three Phase 40 Hp(440 ... 480 V AC) Three Phase 100 hp(550 ... 600 V AC) Three Phase 50 Hp(550 ... 600 V AC) Three Phase 125 hp

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900