ABB
1SFL557025R7211
GAF300-10-11 20-60V DC Contactor
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€881.27
1
Payment methods:
A total of 200 Parts In-Stock from 10 Distributors
Product Conditions:
Dimensions
- Product Net Width
- 140 mm
- Product Net Depth / Length
- 180.5 mm
- Product Net Height
- 227 mm
- Product Net Weight
- 5.5 kg
Technical
- Number of Main Contacts NO
- 1
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 1
- Number of Auxiliary Contacts NC
- 1
- Rated Operational Voltage
- Main Circuit 1000 V
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 500 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
- Rated Operational Current DC-1 (Ie)
- (1000 V) 3 Poles in Series, 40 °C 500 A(1000 V) 3 Poles in Series, 55 °C 400 A(1000 V) 3 Poles in Series, 70 °C 325 A(220 V) 3 Poles in Series, 40 °C 500 A(220 V) 3 Poles in Series, 55 °C 400 A(220 V) 3 Poles in Series, 70 °C 325 A(400 V) 3 Poles in Series, 40 °C 500 A(400 V) 3 Poles in Series, 55 °C 400 A(400 V) 3 Poles in Series, 70 °C 325 A(600 V) 3 Poles in Series, 40 °C 500 A(600 V) 3 Poles in Series, 55 °C 400 A(600 V) 3 Poles in Series, 70 °C 325 A
- Rated Insulation Voltage (Ui)
- acc. to UL/CSA 1000 V
- Rated Impulse Withstand Voltage (Uimp)
- Main Circuit 8 kV
- Mechanical Durability
- 5 million
- Maximum Mechanical Switching Frequency
- 300 cycles per hour
- Coil Operating Limits
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
- Rated Control Circuit Voltage (Uc)
- DC Operation 20 ... 60 V
- Coil Consumption
- Holding at Max. Rated Control Circuit Voltage 50 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage DC 520 V·A
- Connecting Capacity Main Circuit
- Bar 32 mm²Rigid Al-Cable 2 x 95 ... 120 mm²Rigid Cu-Cable 16 ... 240 mm²
- Connecting Capacity Auxiliary Circuit
- Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 1 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
- Terminal Type
- Main Circuit: Bars
Classifications
- Object Classification Code
- Q
- ETIM 4
- EC002552 - Power contactor, DC switching
- ETIM 5
- EC002552 - Power contactor, DC switching
- EClass
- V11.0 : 27371018
- IDEA Granular Category Code (IGCC)
- 4763 >> Power contactor, DC switching
Environmental
- Ambient Air Temperature
- Operation -40 ... +80 °CStorage -40 ... +70 °C
- Maximum Operating Altitude Permissible
- Without Derating 3000 m
- Resistance to Shock acc. to IEC 60068-2-27
- Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- Main Circuit 600 V
- General Use Rating UL/CSA
- (1000 V DC) 400 A(440 V DC) 400 A(600 V DC) 400 A
Ordering
- Minimum Order Quantity
- 1 piece
- Customs Tariff Number
- 85364900
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther