1SFL587102R1111

AF305-40-11-11 Contactor
1SFL587102R1111
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Dimensions

Product Net Width
184 mm
Product Net Depth / Length
180 mm
Product Net Height
225.4 mm
Product Net Weight
5.7 kg

Technical

Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 500 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 375 A(1000 V) 60 °C 325 A(1000 V) 70 °C 260 A(690 V) 40 °C 500 A(690 V) 60 °C 400 A(690 V) 70 °C 325 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 305 A(440 V) 55 °C 305 A(380 / 400 V) 55 °C 305 A(220 / 230 / 240 V) 55 °C 305
Rated Operational Power AC-3 (Pe)
(415 V) 160 kW(440 V) 160 kW(380 / 400 V) 160 kW(220 / 230 / 240 V) 90 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 630 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 8.5 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 8.5 V·AHolding at Max. Rated Control Circuit Voltage DC 3 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 475 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 475 V·APull-in at Max. Rated Control Circuit Voltage DC 400 W
Operate Time
Between Coil De-energization and NO Contact Opening 45 ... 80 msBetween Coil Energization and NO Contact Closing 30 ... 60 ms
Connecting Capacity Main Circuit
Flexible 2 x 70 ... 185 mm²Rigid Al-Cable 1 x 185 ... 240 mm²Rigid Cu-Cable 2 x 70 ... 185 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars

Eco Transparency

Environmental Product Declaration - EPD
1SFC100104D0201

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707232
E-Number (Norway)
4117788
E-Number (Sweden)
3210342

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value

ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 76.3 %
End of Life Instructions
1SFC100112M0001
Group Waste to Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
Improved Resource Efficiency for Customers
Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Sustainable Material Content
Recycled Metal - 33 %

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(600 V AC) 350 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 40 Hp(200 V AC) Three Phase 100 hp(208 V AC) Three Phase 100 hp(220 ... 240 V AC) Three Phase 50 Hp(220 ... 240 V AC) Three Phase 125 hp(440 ... 480 V AC) Three Phase 100 Hp(440 ... 480 V AC) Three Phase 250 hp(550 ... 600 V AC) Three Phase 150 Hp(550 ... 600 V AC) Three Phase 300 hp

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900