ABB

1SFL647025R6911

GAF1250-10-11 48-130V 50/60Hz / 48-130V DC Contactor
1SFL647025R6911
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€3,181.29
1
Payment methods:
A total of 200 Parts In-Stock from 10 Distributors

Additional Information

Part Number
1SFL647025R6911
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, DC switching
Class Code : EC002552
Version : 7

Dimensions

Product Net Width
210 mm
Product Net Depth / Length
242 mm
Product Net Height
344 mm
Product Net Weight
15 kg

Technical

Number of Main Contacts NO
1
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1260 A
Rated Operational Current DC-1 (Ie)
(1000 V) 3 Poles in Series, 40 °C 1250 A(1000 V) 3 Poles in Series, 55 °C 1040 A(1000 V) 3 Poles in Series, 70 °C 875 A(220 V) 3 Poles in Series, 40 °C 1250 A(220 V) 3 Poles in Series, 55 °C 1040 A(220 V) 3 Poles in Series, 70 °C 875 A(400 V) 3 Poles in Series, 40 °C 1250 A(400 V) 3 Poles in Series, 55 °C 1040 A(400 V) 3 Poles in Series, 70 °C 875 A(600 V) 3 Poles in Series, 40 °C 1250 A(600 V) 3 Poles in Series, 55 °C 1040 A(600 V) 3 Poles in Series, 70 °C 875 A
Rated Insulation Voltage (Ui)
acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
0.5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 4.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 850 V·APull-in at Max. Rated Control Circuit Voltage DC 950 V·A
Connecting Capacity Main Circuit
Bar 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 1 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars

Classifications

Object Classification Code
Q
ETIM 4
EC002552 - Power contactor, DC switching
ETIM 5
EC002552 - Power contactor, DC switching
EClass
V11.0 : 27371018
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching

Environmental

Ambient Air Temperature
Operation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(1000 V DC) 1210 A(440 V DC) 1210 A(600 V DC) 1210 A

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900