ABB

AF185B-30-11-69

AF185B-30-11 48-130V 50/60Hz / DC Contactor
AF185B-30-11-69
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Additional Information

Part Number
AF185B-30-11-69
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7

Dimensions

Product Net Width
111.5 mm
Product Net Depth / Length
160 mm
Product Net Height
196 mm
Product Net Weight
3 kg

Technical

Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 200 A(1000 V) 55 °C 200 A(1000 V) 70 °C 180 A(690 V) 40 °C 275 A(690 V) 55 °C 250 A(690 V) 70 °C 180 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 185 A(440 V) 55 °C 185 A(500 V) 55 °C 170 A(690 V) 55 °C 170 A(1000 V) 55 °C 95 A(380 / 400 V) 55 °C 185 A(220 / 230 / 240 V) 55 °C 185
Rated Operational Power AC-3 (Pe)
(415 V) 90 kW(440 V) 90 kW(500 V) 110 kW(690 V) 132 kW(1000 V) 132 kW(380 / 400 V) 90 kW(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 160 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1600 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 430 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 430 V·APull-in at Max. Rated Control Circuit Voltage DC 500 W
Operate Time
Between Coil De-energization and NC Contact Closing 40 ... 50 msBetween Coil De-energization and NO Contact Opening 43 ... 53 msBetween Coil Energization and NC Contact Opening 45 ... 85 msBetween Coil Energization and NO Contact Closing 50 ... 90 ms
Connecting Capacity Main Circuit
Bar 24 mm²Rigid Al-Cable 25 ... 150 mm²Rigid Cu-Cable 6 ... 185 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting Terminals (delivered in open position) Main Poles
Flat type c/w screws and bolts
Terminal Type
Main Circuit: Bars

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4755 >> Contactors

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
RoHS Status
Following EU Directive 2011/65/EU

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 250 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 50 hp(208 V AC) Three Phase 50 hp(220 ... 240 V AC) Three Phase 60 hp(440 ... 480 V AC) Three Phase 125 hp(550 ... 600 V AC) Three Phase 150 hp

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Replacement Product ID (NEW)
1SFL487063R1222