ABB

AF80-30-22-41

AF80-30-22-41 24-60V50/60HZ Contactor
AF80-30-22-41
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Additional Information

Part Number
AF80-30-22-41
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, AC switching
Class Code : EC000066
Version : 7

Dimensions

Product Net Width
70 mm
Product Net Depth / Length
149 mm
Product Net Height
125.5 mm
Product Net Weight
1.27 kg

Technical

Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22
Rated Operational Voltage
Auxiliary Circuit 690 VMain Circuit 1000 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 HzControl Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 Aacc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 125 A(690 V) 60 °C 100 A(690 V) 70 °C 85 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 80 A(440 V) 60 °C 80 A(500 V) 60 °C 65 A(690 V) 60 °C 49 A(1000 V) 60 °C 25 A(380 / 400 V) 60 °C 80 A(220 / 230 / 240 V) 60 °C 80 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 80 A(440 V) 60 °C 80 A(500 V) 60 °C 65 A(690 V) 60 °C 49 A(380 / 400 V) 60 °C 80 A(220 / 230 / 240 V) 60 °C 80 A
Rated Operational Power AC-3 (Pe)
(400 V) 37 kW(415 V) 45 kW(440 V) 45 kW(500 V) 45 kW(690 V) 45 kW(1000 V) 35 kW(380 / 400 V) 37 kW(220 / 230 / 240 V) 22 kW
Rated Operational Power AC-3e (Pe)
(415 V) 45 kW(440 V) 45 kW(500 V) 45 kW(690 V) 45 kW(380 / 400 V) 37 kW(220 / 230 / 240 V) 22 kW
Rated Operational Current AC-15 (Ie)
(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 Afor 0.1 s 140 Afor 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
Maximum Electrical Switching Frequency
(AC-1) 600 cycles per hour(AC-15) 1200 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour(DC-13) 900 cycles per hour
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A(110 V) 2 Poles in Series, 60 °C 100 A(110 V) 2 Poles in Series, 70 °C 85 A(110 V) 3 Poles in Series, 40 °C 125 A(110 V) 3 Poles in Series, 60 °C 100 A(110 V) 3 Poles in Series, 70 °C 85 A(220 V) 3 Poles in Series, 40 °C 125 A(220 V) 3 Poles in Series, 60 °C 100 A(220 V) 3 Poles in Series, 70 °C 85 A(72 V) 1-Pole, 40 °C 125 A(72 V) 1-Pole, 60 °C 100 A(72 V) 1-Pole, 70 °C 85 A(72 V) 2 Poles in Series, 40 °C 125 A(72 V) 2 Poles in Series, 60 °C 100 A(72 V) 2 Poles in Series, 70 °C 85 A(72 V) 3 Poles in Series, 40 °C 125 A(72 V) 3 Poles in Series, 60 °C 100 A(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A(110 V) 2 Poles in Series, 60 °C 100 A(110 V) 2 Poles in Series, 70 °C 85 A(110 V) 3 Poles in Series, 40 °C 125 A(110 V) 3 Poles in Series, 60 °C 100 A(110 V) 3 Poles in Series, 70 °C 85 A(220 V) 3 Poles in Series, 40 °C 125 A(220 V) 3 Poles in Series, 60 °C 100 A(220 V) 3 Poles in Series, 70 °C 85 A(72 V) 1-Pole, 40 °C 125 A(72 V) 1-Pole, 60 °C 100 A(72 V) 1-Pole, 70 °C 85 A(72 V) 2 Poles in Series, 40 °C 125 A(72 V) 2 Poles in Series, 60 °C 100 A(72 V) 2 Poles in Series, 70 °C 85 A(72 V) 3 Poles in Series, 40 °C 125 A(72 V) 3 Poles in Series, 60 °C 100 A(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 125 A(110 V) 2 Poles in Series, 60 °C 100 A(110 V) 2 Poles in Series, 70 °C 85 A(110 V) 3 Poles in Series, 40 °C 125 A(110 V) 3 Poles in Series, 60 °C 100 A(110 V) 3 Poles in Series, 70 °C 85 A(220 V) 3 Poles in Series, 40 °C 125 A(220 V) 3 Poles in Series, 60 °C 100 A(220 V) 3 Poles in Series, 70 °C 85 A(72 V) 1-Pole, 40 °C 125 A(72 V) 1-Pole, 60 °C 100 A(72 V) 1-Pole, 70 °C 85 A(72 V) 2 Poles in Series, 40 °C 125 A(72 V) 2 Poles in Series, 60 °C 100 A(72 V) 2 Poles in Series, 70 °C 85 A(72 V) 3 Poles in Series, 40 °C 125 A(72 V) 3 Poles in Series, 60 °C 100 A(72 V) 3 Poles in Series, 70 °C 85 A
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 1000 Vacc. to IEC 60947-5-1 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Mechanical Switching Frequency
3600 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation -
Operate Time
Between Coil De-energization and NC Contact Closing 19 ... 105 msBetween Coil De-energization and NO Contact Opening 17 ... 100 msBetween Coil Energization and NC Contact Opening 38 ... 95 msBetween Coil Energization and NO Contact Closing 42 ... 100 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)
2 x M4 or 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 6 ... 50 mm²Flexible with Insulated Ferrule 1/2x 6 ... 50 mm²Rigid Stranded 1x 6 ... 70 mm²Rigid Stranded 2x 6 ... 50 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control Circuit
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length
Auxiliary Circuit 10 mmControl Circuit 10 mmMain Circuit 17 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type
Screw Terminals

Classifications

Object Classification Code
Q
ETIM 4
EC000066 - Magnet contactor, AC-switching
ETIM 5
EC000066 - Magnet contactor, AC-switching
EClass
V11.0 : 27371003
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707129

Environmental

Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations acc. to IEC 60068-2-6
5 ... 300 Hz 3 g closed position / 3 g open position
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: A 25 gClosed, Shock Direction: B1 25 gClosed, Shock Direction: B2 15 gClosed, Shock Direction: C1 25 gClosed, Shock Direction: C2 25 gOpen, Shock Direction: B1 5 g
RoHS Status
Following EU Directive 2011/65/EU

Technical UL/CSA

NEMA Size
3
Continuous Current Rating NEMA
90 A
Horsepower Rating NEMA
(200 V AC) Three Phase 25 Hp(230 V AC) Three Phase 30 Hp(460 V AC) Three Phase 50 Hp(575 V AC) Three Phase 50 Hp
General Use Rating UL/CSA
(600 V AC) 105 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 7-1/2 hp(200 ... 208 V AC) Three Phase 25 hp(220 ... 240 V AC) Three Phase 30 hp(240 V AC) Single Phase 15 hp(440 ... 480 V AC) Three Phase 60 hp(550 ... 600 V AC) Three Phase 75 hp
Connecting Capacity Main Circuit UL/CSA
Rigid Stranded 1/2x 6-1 AWG
Tightening Torque UL/CSA
Auxiliary Circuit 11 in·lbControl Circuit 11 in·lbMain Circuit 53 in·lb

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900