Dimensions

Product Frame Size
S
Product Net Width
150 mm
Product Net Height
176 mm6.9 in
Product Net Depth / Length
84 mm3.3 in
Product Net Weight
1.7 kg3.7 lb

Technical

Connection Configuration
Single circuit 1a
Rated Operational Current DC-21B (Ie)
(1000 V) 160 A
Conventional Free-air Thermal Current (Ith)
160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1500 V
Rated Operational Voltage
1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V DC) 10 kA
Rated Short-time Withstand Current (Icw)
1000 V DC 10 kAfor 1 s 5 kAfor 0.1 s 10 kA
Protection Type
Circuit breaker
Power Loss
at Rated Operating Conditions per Pole 4 W
Pollution Degree
3
Handle Color
Black
Handle Length
65 mm2.6 in
Handle Type
Pistol handle
Shaft Diameter
6 mm0.24 in
Shaft Length
210 mm8.3 in
Switches Operating Mechanism
Mechanism Between the Poles11 (Between the Poles)
Position of Line Terminals
Bottom In - Bottom Out
Operating Mode
Front Operated
Standards
UL98B and IEC 60947-1, -3
Special Functions
US single-wire break
Mounting Type
Base mounting
Number of Circuits
1
Number of Poles
2
Degree of Protection
Front IP20
Terminal Type
Lug terminals
Terminal Width
19.5 mm0.77 in
Tightening Torque
Cable Lug 15…22 N·m

Container Information

Package Level 1 Units
box 1 piece
Package Level 1 Width
96 mm3.8 in
Package Level 1 Depth / Length
160 mm6.3 in
Package Level 1 Height
244 mm9.6 in
Package Level 1 Gross Weight
1.8 kg3.9 lb
Package Level 1 EAN
6417019561479

Classifications

Object Classification Code
Q
ETIM 5
EC000216 - Switch disconnector
ETIM 6
EC000216 - Switch disconnector
ETIM 7
EC000216 - Switch disconnector
UNSPSC
39122233
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)

Environmental

RoHS Status
Following EU Directive 2011/65/EU
Environmental Information
NA

Technical UL/CSA

Maximum Operating Voltage UL/CSA
1000 V DC
Ampere Rating UL/CSA
1000VDC 100 A
Tightening Torque UL/CSA
Cable Lug 10…12 N·mCable Lug 133…195 lbf·in