Fluke

1623-2 Kit

The Fluke 1623-2 Earth Ground Tester Kit offers fast, accurate earth ground tests using all 4 test methods. World class accessories speed set up and test time.
1623-2 Kit
1623-2 Kit
1623-2 Kit
1623-2 Kit
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers

Measure frequency
128 Hz
Noise current (IEXT)
Automatic range selection. The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.
Noise current (IEXT)
Max. IEXT = 10 A (AC) (RA < 20 Ω)
Measuring voltage
Vm = 48 V AC
Noise current (IEXT)
Max. IEXT = 2 A (AC) (RA > 20 Ω)

Temperature Range

External voltage
V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
Auxiliary power
6 x 1.5 V Alkaline (type AA LR6)
Max. overload
250 V rms (pertains to misuse)
Intrinsic error
Refers to the reference temperature range and is guaranteed for 1 year
Temperature coefficient
±0.1% of reading/°C < 18°C > 28°C
Dimensions (W x H x D)
250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
EMC (emission immunity)
IEC61326-1: Portable
Quality system
Developed, designed and manufactured according to DIN ISO 9001
Safety
Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree 2
Climatic class
C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Weight
1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
Protective type
IP56 for case, IP40 for battery door according to EN60529
Operating error
Refers to the operating temperature range and is guaranteed for 1 year
Battery life span
Typical > 3,000 measurements
Operating temperature
-10°C to 50°C (14°F to 122°F)
V ext rejection
> 120 dB (162⁄3, 50, 60, 400 Hz)
Measuring time
Typical 6 seconds
Storage temperature
-30°C to 60°C (-22°F to 140°F)

RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (R

Measuring range
0.020 Ω to 19.99 kΩ
Operating error
±(10% rdg + 5 d)
Switch position
RA 3-pole with clamp
Resolution
0.001 Ω to 10 Ω
Accuracy
±(7% rdg + 3 d)

Stakeless Ground Loop Measurement (2 Clamps )

Switch position
RA 4-pole 2 clamps
Accuracy
±(7% rdg + 3 d)
Resolution
0.001 Ω to 10 Ω
Operating error
±(10% rdg + 5 d)
Measuring range
0.020 Ω to 19.99 kΩ

RA 3-Pole Ground Resistance Measurement (IEC 1557-5)

Measuring range
0.020 Ω to 19.99 kΩ
Switch position
RA 3-pole
Operating error
±(5% rdg + 3 d)
Resolution
0.001 Ω to 10 Ω
Accuracy
±(2% rdg + 3 d)

Measuring Principle: Current/Voltage Measurement (with External Current Clamp)

Probe resistance (RS)
Max 100 kΩ
Measuring voltage
Vm = 48 V AC
Measure frequency
128 Hz
Short-circuit current
> 50 mA
Short-circuit current
> 50 mA
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Probe resistance (RS)
Max 100 kΩ
Measure frequency
128 Hz
Measuring voltage
Vm = 48 V AC
Auxiliary earth electrode resistance (RH)
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.
Auxiliary earth electrode resistance (RH)
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.
Auxiliary earth electrode resistance (RH)
Max 100 kΩ

R

Accuracy
±(2% rdg + 3 d)
Measuring range
0.020 Ω to 19.99 kΩ
Resolution
0.001 Ω to 10 Ω
Operating error
±(5% rdg + 3 d)
Switch position
RA 4-pole

Measuring Principle: Current/Voltage Measurement

Probe resistance (RS + RES)
Max 100 kΩ
Additional error from RH and RS
Monitoring of RS and RH with error indicator. Automatic range selection.
Additional error from RH and RS
RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Measure frequency
128 Hz
Short-circuit current
> 50 mA
Measuring voltage
Vm = 48 V AC
Short-circuit current
> 50 mA
Probe resistance (RS)
Max 100 kΩ
Additional error from RH and RS
RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Measuring voltage
Vm = 48 V AC
Additional error from RH and RS
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Measure frequency
128 Hz

RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (R

Operating error
±(10% rdg + 5 d)
Resolution
0.001 Ω to 10 Ω
Measuring range
0.020 Ω to 19.99 kΩ
Accuracy
±(7% rdg + 3 d)
Switch position
RA 4-pole with clamp

General Specifications

User interface
Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Memory
Internal memory storage up to 1500 records accessible via USB port
Display: 1999 digit LCD
Display with special symbols, digit height 25 mm, fluorescent backlight
Robust, water and dust resistant
Instrument is designed for tough environmental conditions (rubber protective cover, IP56)