Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers

Noise current (IEXT)
Max. IEXT = 10 A (AC) (RA < 20 Ω)
Noise current (IEXT)
Automatic range selection. The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum distance specified.
Measuring voltage
Vm = 48 V AC
Noise current (IEXT)
Max. IEXT = 2 A (AC) (RA > 20 Ω)
Measure frequency
128 Hz

Temperature Range

Max. overload
250 V rms (pertains to misuse)
Climatic class
C1 (IEC 654-1), -5°C to +45°C (23° to +115° F), 5% to 95% RH
Protective type
IP56 for case, IP40 for battery door according to EN60529
Battery life span
Typical > 3,000 measurements
Quality system
Developed, designed and manufactured according to DIN ISO 9001
Operating error
Refers to the operating temperature range and is guaranteed for 1 year
EMC (emission immunity)
IEC61326-1: Portable
Intrinsic error
Refers to the reference temperature range and is guaranteed for 1 year
External voltage
V ext, max = 24 V (DC, AC < 400 Hz), measurement inhibited for higher values
Measuring time
Typical 6 seconds
Safety
Protection by double and/or reinforced insulation. max. 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree 2
Operating temperature
-10°C to 50°C (14°F to 122°F)
Dimensions (W x H x D)
250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
V ext rejection
> 120 dB (162⁄3, 50, 60, 400 Hz)
Storage temperature
-30°C to 60°C (-22°F to 140°F)
Temperature coefficient
±0.1% of reading/°C < 18°C > 28°C
Weight
1.1 kg (2.43 lb) including batteries 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
Auxiliary power
6 x 1.5 V Alkaline (type AA LR6)

RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (R

Measuring range
0.020 Ω to 19.99 kΩ
Resolution
0.001 Ω to 10 Ω
Operating error
±(10% rdg + 5 d)
Accuracy
±(7% rdg + 3 d)
Switch position
RA 3-pole with clamp

RA 3-Pole Ground Resistance Measurement (IEC 1557-5)

Measuring range
0.020 Ω to 19.99 kΩ
Resolution
0.001 Ω to 10 Ω
Accuracy
±(2% rdg + 3 d)
Switch position
RA 3-pole
Operating error
±(5% rdg + 3 d)

Measuring Principle: Current/Voltage Measurement (with External Current Clamp)

Probe resistance (RS)
Max 100 kΩ
Short-circuit current
> 50 mA
Measuring voltage
Vm = 48 V AC
Auxiliary earth electrode resistance (RH)
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.
Short-circuit current
> 50 mA
Auxiliary earth electrode resistance (RH)
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Measure frequency
128 Hz
Measure frequency
128 Hz
Measuring voltage
Vm = 48 V AC
Probe resistance (RS)
Max 100 kΩ
Auxiliary earth electrode resistance (RH)
Max 100 kΩ

R

Switch position
RA 4-pole
Accuracy
±(2% rdg + 3 d)
Operating error
±(5% rdg + 3 d)
Measuring range
0.020 Ω to 19.99 kΩ
Resolution
0.001 Ω to 10 Ω

Measuring Principle: Current/Voltage Measurement

Additional error from RH and RS
Monitoring of RS and RH with error indicator. Automatic range selection.
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Additional error from RH and RS
RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Measuring voltage
Vm = 48 V AC
Measure frequency
128 Hz
Probe resistance (RS)
Max 100 kΩ
Measure frequency
128 Hz
Auxiliary earth electrode resistance (RH)
Max 100 kΩ
Probe resistance (RS + RES)
Max 100 kΩ
Measuring voltage
Vm = 48 V AC
Short-circuit current
> 50 mA
Additional error from RH and RS
RH[kΩ]•••RS[kΩ]/RA[Ω]•••0.2%
Short-circuit current
> 50 mA
Additional error from RH and RS
Monitoring of RS and RH with error indicator. Automatic range selection. Measurement is not performed if the current through the current clamp is too low.

RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (R

Measuring range
0.020 Ω to 19.99 kΩ
Resolution
0.001 Ω to 10 Ω
Operating error
±(10% rdg + 5 d)
Accuracy
±(7% rdg + 3 d)
Switch position
RA 4-pole with clamp

General Specifications

Memory
Internal memory storage up to 1500 records accessible via USB port
User interface
Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, water and dust resistant
Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Display: 1999 digit LCD
Display with special symbols, digit height 25 mm, fluorescent backlight

Stakeless Ground Loop Measurement (2 Clamps)

Operating error
±(10% rdg + 5 d)
Switch position
RA 4-pole 2 clamps
Resolution
0.001 Ω to 10 Ω
Accuracy
±(7% rdg + 3 d)
Measuring range
0.020 Ω to 19.99 kΩ