Fluke

1736/B

The Fluke 1736 three-phase power logger is ideal for conducting basic energy and power quality studies.
1736/B
1736/B
1736/B
1736/B
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Current Inputs

Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
Range
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
Range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
Range
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Scaling
1:1 and variable
Number of inputs
4, mode selected automatically for attached sensor
Input voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range

Wireless Connection

Acquisition
1 reading/s
Number of inputs
2
Supported modules
Fluke Connect® 3000 series

Data Acquisition

Circuit types
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Memory size
¹The number of possible logging sessions and logging period depends on user requirements.
Data storage
Internal flash memory (not user replaceable)
Resolution
16-bit synchronous sampling
Input signal frequency
50/60 Hz (42.5 to 69 Hz)
Sampling frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Memory size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹

Auxiliary Inputs

Scale factor (available 2014)
Format: mx + b (gain and offset) user configurable
Number of inputs
2
Input range
0 to ±10 V dc, 1reading/s
Displayed units (available 2014)
User configurable (7 characters, for example, °C, psi, or m/s)

Standards Compliance

Power quality compliance
EN50160 (for measured parameters)
Harmonics
IEC 61000-4-7: Class 1
Harmonics
IEEE 519 (short time harmonics)
Power
IEEE 1459
Power quality
IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)

Voltage Inputs

Number of inputs
4 (3 phases and neutral)
Maximum input voltage
1000 Vrms, CF 1.7
Input impedance
10 MΩ
Scaling
1:1 and variable
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Measurement category
1000 V CAT III/600 V CAT IV

Basic Interval

Measured parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging time min/max values
Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms
Averaging interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min

Interfaces

WiFi
File transfer and remote control via direct connection or WiFi infrastructure
USB-A
File transfer via USB flash drive, firmware updates Max. current: 120 mA
Bluetooth
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-mini
Data download device to PC

Environmental Specifications

Electromagnetic compatibility
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
Electromagnetic compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Temperature coefficient
0.1 x accuracy specification/°C
Electromagnetic compatibility
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Safety
IEC 61010-1
Operating humidity
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
Operating humidity
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Operating altitude
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Operating temperature
-10 °C to +50 °C (14 °F to 122 °F)
Enclosure
IP50 in accordance with EN60529
Storage altitude
12,000m
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Safety
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
Safety
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Operating humidity
10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
Safety
IEC Mains Input: Overvoltage Category II, Pollution Degree 2

Electrical Specifications

Efficiency
≥ 68.2% (in accordance with energy efficiency regulations)
Voltage range
100 V to 500 V using safety plug input when powering from the measurement circuit
Charging time
< 6 hours
Mains power frequency
50/60 Hz ±15%
Maximum no-load consumption
< 0.3 W only when powered using IEC 60320 input
On-battery runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Voltage range
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable

Power Quality Measurements

Triggered recordings
Waveform of voltage and current
Averaging interval
10 min
Total harmonic distortion
Calculated on 50 harmonics
Measured parameter
Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Events
Voltage: dips, swells, interruptions, current: inrush current
Individual harmonics
2nd to 50th harmonic
Triggered recordings
Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)

Demand Interval (Energy Meter Mode)

Measured parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off

General Specifications

Warranty
Accessories: one-year
Dimensions
Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Color LCD display
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty
Calibration cycle: two-years
Dimensions
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Weight
Instrument: 1.1 kg (2.5 lb)
Tamper protection
Kensington lock slot
Dimensions
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Warranty
Instrument and power supply: Two-years (battery not included)
Weight
Power supply: 400 g (0.9 lb)

i17xx-flex 1500 12" Flexible Current Probe Specifications

Probe cable length
305 mm (12 in)
Operating temperature
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Relative humidity, operating
15% to 85% non-condensing
Intrinsic error at reference condition*
±0.7% of reading
Weight
115 g
Warranty
One-year
Warranty
Reference condition: Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65% Primary conductor in center position
Output cable
TPR/PVC
Probe cable material
TPR
Working voltage
1000 V CAT III, 600 V CAT IV
Measuring range
1 to 150 A ac/10 to 1500 A ac
Temperature, non-operating
-40 °C to +80 °C (-40 °F to 176 °F)
Coupling material
POM + ABS/PC
IP rating
IEC 60529:IP50
Accuracy 173x + iFlex
±(1% of reading + 0.02% of range)
Temperature coefficient over operating temperature range
0.05% of reading/°C 0.09% of reading/°F
Nondestructive current
100 kA (50/60 Hz)
Probe cable diameter
7.5 mm (0.3 in)
Output cable length
2 m (6.6 ft)
Minimum bending radius
38 mm (1.5 in)