Fluke

1736/INTL

The Fluke 1736 three-phase power logger is ideal for conducting basic energy and power quality studies.
1736/INTL
1736/INTL
1736/INTL
1736/INTL
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Current Inputs

Range
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
Input voltage
Clamp input: 500 mVrms/50 mVrms; CF 2.8
Range
1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
Range
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
Range
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Scaling
1:1 and variable
Number of inputs
4, mode selected automatically for attached sensor
Rogowski coil input
150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz

Wireless Connection

Number of inputs
2
Acquisition
1 reading/s
Supported modules
Fluke Connect® 3000 series

Data Acquisition

Resolution
16-bit synchronous sampling
Circuit types
1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies)
Memory size
Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹
Memory size
¹The number of possible logging sessions and logging period depends on user requirements.
Data storage
Internal flash memory (not user replaceable)
Sampling frequency
10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency
50/60 Hz (42.5 to 69 Hz)

Auxiliary Inputs

Scale factor (available 2014)
Format: mx + b (gain and offset) user configurable
Number of inputs
2
Input range
0 to ±10 V dc, 1reading/s
Displayed units (available 2014)
User configurable (7 characters, for example, °C, psi, or m/s)

Standards Compliance

Power quality compliance
EN50160 (for measured parameters)
Power quality
IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Harmonics
IEEE 519 (short time harmonics)
Harmonics
IEC 61000-4-7: Class 1
Power
IEEE 1459

Voltage Inputs

Input impedance
10 MΩ
Bandwidth (-3 dB)
42.5 Hz - 3.5 kHz
Number of inputs
4 (3 phases and neutral)
Maximum input voltage
1000 Vrms, CF 1.7
Measurement category
1000 V CAT III/600 V CAT IV
Scaling
1:1 and variable

Basic Interval

Measured parameters
Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging interval
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values
Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms

Interfaces

WiFi
File transfer and remote control via direct connection or WiFi infrastructure
USB-mini
Data download device to PC
Bluetooth
Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option)
USB-A
File transfer via USB flash drive, firmware updates Max. current: 120 mA

Environmental Specifications

Enclosure
IP50 in accordance with EN60529
Operating altitude
2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Safety
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility
EN 61326-1: Industrial CISPR 11: Group 1, Class A
Vibration
MIL-T-28800E, Type 3, Class III, Style B
Storage altitude
12,000m
Safety
IEC Mains Input: Overvoltage Category II, Pollution Degree 2
Operating humidity
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH
Safety
IEC 61010-1
Operating humidity
10 °C to 30 °C (50 °F to 86 °F) max. 95% RH
Electromagnetic compatibility
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
Electromagnetic compatibility
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
Safety
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
Operating temperature
-10 °C to +50 °C (14 °F to 122 °F)
Temperature coefficient
0.1 x accuracy specification/°C
Operating humidity
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH
Storage temperature
-20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)

Electrical Specifications

Maximum no-load consumption
< 0.3 W only when powered using IEC 60320 input
Charging time
< 6 hours
On-battery runtime
Four hours in standard operating mode, up to 5.5 hours in power saving mode
Efficiency
≥ 68.2% (in accordance with energy efficiency regulations)
Voltage range
100 V to 500 V using safety plug input when powering from the measurement circuit
Voltage range
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Mains power frequency
50/60 Hz ±15%
Battery
Li-ion 3.7 V, 9.25 Wh, customer-replaceable

Power Quality Measurements

Total harmonic distortion
Calculated on 50 harmonics
Triggered recordings
Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30)
Triggered recordings
Waveform of voltage and current
Measured parameter
Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
Events
Voltage: dips, swells, interruptions, current: inrush current
Individual harmonics
2nd to 50th harmonic
Averaging interval
10 min

Demand Interval (Energy Meter Mode)

Interval
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Measured parameters
Energy (Wh, varh, VAh), PF, maximum demand, cost of energy

General Specifications

Tamper protection
Kensington lock slot
Dimensions
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Dimensions
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Color LCD display
4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty
Instrument and power supply: Two-years (battery not included)
Warranty
Calibration cycle: two-years
Weight
Power supply: 400 g (0.9 lb)
Warranty
Accessories: one-year
Dimensions
Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Weight
Instrument: 1.1 kg (2.5 lb)

i17xx-flex 1500 12" Flexible Current Probe Specifications

Intrinsic error at reference condition*
±0.7% of reading
Warranty
Reference condition: Environmental: 23 °C ±5 °C, no external electrical/magnetic field, RH 65% Primary conductor in center position
Temperature, non-operating
-40 °C to +80 °C (-40 °F to 176 °F)
Measuring range
1 to 150 A ac/10 to 1500 A ac
Probe cable material
TPR
Warranty
One-year
Relative humidity, operating
15% to 85% non-condensing
Working voltage
1000 V CAT III, 600 V CAT IV
Temperature coefficient over operating temperature range
0.05% of reading/°C 0.09% of reading/°F
Nondestructive current
100 kA (50/60 Hz)
Weight
115 g
Probe cable length
305 mm (12 in)
Output cable length
2 m (6.6 ft)
Accuracy 173x + iFlex
±(1% of reading + 0.02% of range)
Coupling material
POM + ABS/PC
Output cable
TPR/PVC
Minimum bending radius
38 mm (1.5 in)
IP rating
IEC 60529:IP50
Operating temperature
-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Probe cable diameter