For added safety and convenience the Fluke 381 Clamp Meter + detachable display allows you to take readings remotely or in tough-to-reach spots. Learn More.
381
381
381
381
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

DC Voltage

Range
600.0 V /1000 V
Resolution
0.1 V / 1 V
Accuracy
1% ± 5 digits

Frequency via Flexible Current Probe

Resolution
0.1 Hz
Accuracy
0.5% ± 5 digits
Range
5.0 to 500.0 Hz
Trigger Level
5 to 20 Hz, ≥ 25 A 20 to 100 Hz, ≥ 20 A 100 to 500 Hz, ≥ 25 A

Mechanical Specifications

Flexible Current Probe Diameter
7.5 mm
Flexible Current Probe Cable Length (head to electronics connector)
1.8 m
Weight
350 g
Size (L x W x H)
277 x 88 x 43 mm (55 mm for remote unit)
Jaw Opening
34 mm

AC Voltage

Accuracy
1.5% ± 5 digits (20 – 500 Hz)
Range
600 V /1000 V
Resolution
0.1 V / 1 V

AC Current via Flexible Current Probe

Range
999.9 A / 2500 A (45 Hz – 500 Hz)
Accuracy
3% ± 5 digits
Crest Factor (50/60 Hz)
3.0 at 1100 A 2.5 at 1400 A 1.42 at 2500 A Add 2% for C.F. > 2
Resolution
0.1 A / 1 A

Environmental Specifications

EMI, RFI, EMC, RF
EN 61326-1:2006, EN 61326-2-2:2006 ETSI EN 300 328 V1.7.1:2006 ETSI EN 300 489 V1.8.1:2008 FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249 FCCID: T68-F381 RSS-210 IC: 6627A-F381
Operating Humidity
Non condensing (< 10°C) ≤ 90% RH (at 10°C to 30°C) ≤ 75% RH (at 30°C to 40°C) ≤ 45% RH (at 40°C to 50°C) (Without Condensation)
Temperature Coefficients
Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C
Operating Temperature
-10°C to +50°C
Wireless Frequency
2.4 GHz ISM Band 10 meter range
Double Insulation Clearance
Per IEC 61010-2-032
Storage Temperature
-40°C to +60°C
Operating Altitude
2,000 meters
Storage Altitude
12,000 meters
Double Insulation Creepage
Per IEC 61010-1
Safety Compliance
ANSI/ISA S82.02.01:2004 CAN/CSA-C22.2 No. 61010-1-04 IEC/EN 61010-1:2001 to 1000V CAT III, 600V CAT IV.

Electrical Specifications

Accuracy
2% ± 5 digits (10-100 Hz) 5% ± 5 digits (100-500 Hz)
Resolution
0.1 A
Range
999.9 A
Crest Factor (50/60 Hz)
3 @ 500 A 2.5 @ 600 A 1.42 @ 1000 A Add 2% for C.F. > 2

Resistance

Range
600 Ω/6 kΩ/60 kΩ
Resolution
0.1 Ω/1 Ω/10 Ω
Accuracy
1% ± 5 digits

Frequency – Via Jaw

Trigger Level
5 – 10 Hz, ≥ 10 A 10 – 100 Hz, ≥ 5 A 100 – 500 Hz, ≥ 10 A
Range
5.0 – 500.0 Hz
Accuracy
0.5% ± 5 digits
Resolution
0.1 Hz

DC Current

Resolution
0.1 A
Range
999.9 A
Accuracy
2% ± 5 digits