Fluke

FLK-1662

FLK-1662
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Continuity testing (RLO)

Range (autoranging)
20 Ω / 200 Ω / 2000 Ω
Resolution
0.01 Ω / 0.1 Ω / 1 Ω
Open Circuit Voltage
>4 V

Tripping speed test (ΔT)

Current settings¹
10-30-100-300-500-1000 mA – VAR10-30-100 mA
Multiplier
x 1/2, x 1x 5
Measurement range RCD Type G
310 ms50 ms
Measurement range RCD Type S
510 ms160 ms
Notes
¹1000 mA type AC only700 mA maximum type A in VAR modeVAR mode not available for type B. || ¹30% to 150% for Type A IΔN > 10 mA30% to 210% for Type A IΔN = 10 mA20% to 210% for Type B
Current range
30% to 110% of RCD rated current¹
Step size
10% of IΔN²
Dwell time Type G
300 ms/step
Dwell time Type S
500 ms/step
Measurement accuracy
±5%
Specified trip current ranges (EN 61008-1)
50% to 100% for Type AC35% to 140% for Type A (>10 mA)35% to 200% for Type A (≤10 mA)50% to 200% for Type B²5% for Type B

RCD testing, RCD types tested

RCD Type
A4, AC¹, G², S³
Notes
¹Responds to AC²General, no delay³Time delay4Responds to pulsed signal5Responds to smooth DC signal

Insulation resistance measurement (RISO)

Accuracy of tTest voltage (at rated test current)
+10%, -0%
Test voltage
100 V250 V500 V1000 V
Insulation resistance range
20 MΩ / 50 MΩ20 MΩ / 100 MΩ20 MΩ / 200 MΩ20 MΩ / 200 MΩ / 500 MΩ20 MΩ / 200 MΩ / 1000 MΩ
Resolution
0.01 MΩ / 0.1 MΩ0.01 MΩ / 0.1 MΩ0.01 MΩ / 0.1 MΩ0.01 MΩ / 0.1 MΩ / 1 MΩ0.01 MΩ / 0.1 MΩ / 1 MΩ
Test current
1 mA @ 50 kΩ1 mA @ 100 kΩ1 mA @ 250 kΩ1 mA @ 500 kΩ1 mA @ 1 MΩ

Phase Sequence Indication

Icon
Phase Sequence indicator is active.

AC voltage measurement

Range
500 V
Resolution
0.1 V
Accuracy 45 Hz – 66 Hz
0.8% + 3
Input impedance
360 kΩ
Overload protection
660 V rms

Loop and line impedance (ZI)

Range
10 Ω / 0.001 Ω / High current mΩ mode || 1000 A / 10 kA (50 kA)
Resolution
0.01 Ω / 0.1 Ω / 1 Ω || 1 A / 0.1 kA
Computation
Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.

General Specifications

Size (L x W x H)
10 x 25 x 12.5 cm
Weight (incl. batteries)
1.3 Kg
Battery size, quantity
Type AA, 6 ea.
Sealing
IP-40
Safety
Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
Overvoltage
CAT III / 500V; CAT IV 300V
Performance
EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

Documents

Data Sheet

Download