Fluke

Fluke 1630-2 FC

Fluke 1630-2 FC
Fluke 1630-2 FC
Fluke 1630-2 FC
Fluke 1630-2 FC
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
10 006,30 zł
1
Payment methods:
A total of 40 Parts In-Stock from 3 Distributors

Earth Ground Loop Resistance

Range
Accuracy1  ± (% of reading + Ω)
0.025 Ω to 0.249 Ω
1.5% + 0.02 Ω
0.250 Ω to 0.999 Ω
1.5% + 0.05 Ω
1.000 Ω to 9.999 Ω
1.5% + 0.10 Ω
10.00 Ω to 49.99 Ω
1.5% + 0.30 Ω
50.00 Ω to 99.99 Ω
1.5% + 0.50 Ω
100.0 Ω to 199.9 Ω
3.0% + 1.0 Ω
200.0 Ω to 399.9 Ω
5.0% + 5.0 Ω
400 Ω to 599 Ω
10.0% + 10 Ω
600 Ω to 1500 Ω
20.00%

Wireless Radio

Frequency range
2412 MHz to 2462 MHz
Output power
<10 mW
Radio frequency certification
FCC ID:T68-FBLE IC:6627A-FBLE

Earth ground leakage current mA

Range Resolution
Accuracy1  ± (% of reading + mA)
0.200 mA to 3.999 mA 1 μA
2.0% + 0.05 mA
4.00 mA to 39.99 mA 10 μA
2.0% + 0.03 mA
40.0 mA to 399.9 mA 100 μA
2.0% + 0.3 mA
0.400 A to 3.999 A
1 mA: 2.0% + 3 mA
4.00 A to 39.99 A
10 mA: 2.0% + 30 mA

Electrical Specifications

Maximum voltage to earth ground
1000 V
Battery type
AA alkaline IEC/EN LR6 (x4)
Battery life
More than 15 hours*
Frequency range
40 Hz to 1 kHz
Ingress protection
IEC/EN 60529: IP30 with jaw closed
LCD
Digital reading: 9999 counts
LCD Refresh rate
4 per second
Operating temperature
-10 °C to + 50 °C
Storage temperature
-20 °C to + 60 °C
Operating humidity
Non condensing (<10 °C) (< 50 °F)   || ≤90% RH (at 10 °C to 30 °C [50 °F to 86 °F]) || ≤75% RH (at 30 °C to 40 °C [86 °F to 104 °F])  || ≤45% RH (at 40 °C to 50 °C [104 °F to 122 °F]) || (Non condensing)
Operating altitude
2000 m (6561 feet)
Storage altitude
12 000 m (39,370 feet)
Reference temperature
23 °C ±5 °C (73 °F ±9 °F)
Temperature coefficient
0.15% x (specified accuracy)/ °C (<18 °C or >28 °C [<64.4 °F or >82.4 °F])
Overload indication
OL
Data logging capacity
Minimum of 32,760 measurements
Data logging interval
1 second to 59 minutes and 59 seconds
Input (Ω)
Minimum: Maximum
0.474 0.417
0.531
0.5 0.443
0.558
10 9.55
10.45
100 96
104

General Specifications

Conductor size
40 mm (1.57 in) approximately
Dimensions (L x W x H)
283 x 105 x 48 mm (11.1 x 4.1 x 1.9 in)
Weight
880g (31 oz)
Warranty
One year

Safety

General
IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
Measurement
IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
Current clamp for leakage current measurements
IEC/EN 61557-13: Class 2, ≤30 A/m
Resistance to earth
IEC/EN 61557-5
Effectiveness of thepProtective measures
IEC/EN 61557-16
Electromagnetic compatibility (EMC) International
IEC/EN 61326-1: Portable Electromagnetic Environment || CISPR 11: Group 1, Class B, IEC/EN 61326-2-2
Electromagnetic compatibility (EMC) Korea (KCC)
Class A equipment (Industrial Broadcast & Communications Equipment)
Electromagnetic compatibility (EMC) USA (FCC)
47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103

Documents

Data Sheet

Download