Fluke
i3000s Flex 24
The i3000s Flex is an ac current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
€695.24
1
Payment methods:
A total of 15 Parts In-Stock from 2 Distributors
Product Conditions:
Electrical Specifications
- Temperature coefficient
- ±0.08% of reading per °C
- Accuracy
- at +25°C: ±1% of range (45 Hz to 65 Hz)
- Linearity
- 10% to 100% of range: ±0.2% of reading
- Current ranges
- 30 A
- Current ranges
- 300 A
- Noise
- 2 mV AC rms (300 A, 3000 A)
- Noise
- 8 mV AC rms (30 A)
- Frequency range
- 10 Hz to 50 kHz (-3 dB)
- Output sensitivity (AC-coupled)
- 1 mV per A
- Output sensitivity (AC-coupled)
- 100 mV
- Current ranges
- 3000 A
- Working voltage
- see Safety standards section: 600 V AC rms or DC
- Output sensitivity (AC-coupled)
- 10 mV
- Position Sensitivity
- with cable > 25 mm from the coupling: ±2% of range
- External field
- with cable > 200 mm from the head: ±1% of range
- Phase error
- < ±1° (45 Hz to 65 Hz)
- Power supply
- 2 x AA/MN 1500/LR6 Alkaline, 400 hours, low battery indicator or dedicated external power supply
- Load impedance
- 100 kΩ minimum
- Phase error
- ±10° (at 20 kHz)
- Current ranges
- AC rms
General Specifications
- Safety standards
- BS EN 61010-2-032: 2002
- Safety standards
- Use of the probe on uninsulated conductors is limited to 600 V AC rms or DC and frequencies below 1 kHz
- Weight
- 190 g (0.419 lb) (electronics)
- Operating temperature range
- -20°C to +90°C (-4°F to 190°F) (head)
- Operating temperature range
- -20°C to +85°C (-4°F to 185°F) (electronics)
- EMC standards
- EN 61326: 1998 +A1, A2, & A3
- Cable length (head to electronics)
- 2 m (6.56 ft)
- Head bend radius
- 38.1 mm (1.5 in)
- Storage temperature range
- -20°C to +85°C (-4°F to 185°F) (electronics)
- Head cable diameter
- 14.3 mm (0.56 in)
- Head circumference
- 610 mm (24 in)
- Safety standards
- BS EN 61010-031: 2002
- Operating humidity
- 15% to 85% (non-condensing)
- Storage temperature range
- -40°C to +105°C (-40°F to 221°F) (head)
- Safety standards
- BS EN 61010-1: 2001
- Safety standards
- 600 Vrms, Category III, Pollution Degree 2
- Maximum conductor size
- 610 mm or 914 mm, depending on model
- Output connection
- 0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
- Weight
- 180 g (0.396 lb) (head)
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther