Fluke

i3000s Flex 24

The i3000s Flex is an ac current clamp utilizing the Rogowski principle. It can be used to measure currents up to 3000 A when used in conjunction with oscilloscopes, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
i3000s Flex 24
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€695.24
1
Payment methods:
A total of 15 Parts In-Stock from 2 Distributors

Electrical Specifications

Temperature coefficient
±0.08% of reading per °C
Accuracy
at +25°C: ±1% of range (45 Hz to 65 Hz)
Linearity
10% to 100% of range: ±0.2% of reading
Current ranges
30 A
Current ranges
300 A
Noise
2 mV AC rms (300 A, 3000 A)
Noise
8 mV AC rms (30 A)
Frequency range
10 Hz to 50 kHz (-3 dB)
Output sensitivity (AC-coupled)
1 mV per A
Output sensitivity (AC-coupled)
100 mV
Current ranges
3000 A
Working voltage
see Safety standards section: 600 V AC rms or DC
Output sensitivity (AC-coupled)
10 mV
Position Sensitivity
with cable > 25 mm from the coupling: ±2% of range
External field
with cable > 200 mm from the head: ±1% of range
Phase error
< ±1° (45 Hz to 65 Hz)
Power supply
2 x AA/MN 1500/LR6 Alkaline, 400 hours, low battery indicator or dedicated external power supply
Load impedance
100 kΩ minimum
Phase error
±10° (at 20 kHz)
Current ranges
AC rms

General Specifications

Safety standards
BS EN 61010-2-032: 2002
Safety standards
Use of the probe on uninsulated conductors is limited to 600 V AC rms or DC and frequencies below 1 kHz
Weight
190 g (0.419 lb) (electronics)
Operating temperature range
-20°C to +90°C (-4°F to 190°F) (head)
Operating temperature range
-20°C to +85°C (-4°F to 185°F) (electronics)
EMC standards
EN 61326: 1998 +A1, A2, & A3
Cable length (head to electronics)
2 m (6.56 ft)
Head bend radius
38.1 mm (1.5 in)
Storage temperature range
-20°C to +85°C (-4°F to 185°F) (electronics)
Head cable diameter
14.3 mm (0.56 in)
Head circumference
610 mm (24 in)
Safety standards
BS EN 61010-031: 2002
Operating humidity
15% to 85% (non-condensing)
Storage temperature range
-40°C to +105°C (-40°F to 221°F) (head)
Safety standards
BS EN 61010-1: 2001
Safety standards
600 Vrms, Category III, Pollution Degree 2
Maximum conductor size
610 mm or 914 mm, depending on model
Output connection
0.5 m cable terminated with safety BNC connector. Supplied with 4mm safety plug adapter
Weight
180 g (0.396 lb) (head)