Fluke

i430

i430
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Current range
3000 A AC rms
Voltage output (@ 1000 A rms, 50 Hz)
85 mV
Position sensitivity
±2% of reading max.
Bandwidth (-3 dB)
10 Hz to 7 kHz
Phase error (45 – 65 Hz)
±1°
Output impedance
82 Ω min
Accuracy
(@ 25°C, 50 Hz)
Linearity (10% to 100% of range)
±0.2% of reading
Accuracy
±1% of reading
Load impedance
50 kΩ
Noise (10 Hz – 7 kHz)
1.0 mV AC rms
Working voltage (see Safety Standards section)
1000 V AC rms or DC (head)
Working voltage (see Safety Standards section)
30 V max. (output)
Internal resistance per 100 mm probe length
10.5 Ω ± 5%
Temperature coefficient
±0.08% max of reading per °C

Safety Specifications

Safety standards
BS EN 61010-2-032 2002
Safety standards
safety rating for the output to earth is limited to 600 V AC rms or DC.
Safety standards
Use of the probe on uninsulated conductors is limited to 1000 V AC rms or DC and frequencies below 1 kHz.
Safety standards
Please note that this probe is designed to work with Fluke 435, if used with other products
Safety standards
BS EN 61010-031 2002, 1000 Vrms, Category III, Pollution Degree 2
Safety standards
BS EN 61010-1 2001

General Specifications

Operating range
-20 to +90°C
Couplings material
Polypropylene, UL94 V-0
Probe and cable material
UL94 V-0, Colour: RED Munsell 7.5
Output cable length
2.5 meters RG58
Probe cable diameter
12.4 mm
Output connector
Safety BNC Connector
Degree of protection (Probe)
IP41
Probe and cable material
TPE rubber, reinforced insulation
Probe cable bend radius
40 mm
Storage temperature
-40 to +105°C
Probe cable length
610 mm
Probe and cable material
R 1/14
Operating humidity
15% to 85% (non condensing)