Current sensor, Industrial version, IPM Primary current, measuring range: ‌0 ... ±,300 A, KN Turns ratio: 1 : 2000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Technical characteristics

I PN Nominal primary current
200 A
I PM Primary current, measuring range
[‌0] ... [±300 A]
R M Measuring resistance @ I PM max , U C max , T A max
5 ... ‌58 Ω For other primary currents see diagram.
I SN Nominal secondary current
100 mA
K N Turns ratio
1 : 2000
U C Power supply
±12 ... ±15 V ±5 %
I C Current consumption @ U C min
19 mA + I
X Overall accuracy @ I PN , T A = 25 °C
± 0.8 %
Ε L Linearity
< 0.1 %
I O Offset current @ I P = 0 A, T A = 25 °C
± 0.3 mA
I OT maximum temperature drift of I O
± 0.8 mA
T r Response time @ I PN
< 1 µs
Di/dt with optimal coupling
> 100 A/µs
F Frequency
0 ... 100 kHz
T A Ambient temperature
-40 ... +85 °C
T S Storage temperature
-45 ... +90 °C
R S Secondary coil resistance @ T A max
25 Ω
U D Test voltage, effective (50 Hz, 1 min)
3 kV Primary - secondary
U St Rated impulse voltage (1,2/50 µs)
10 kV
U B Rated voltage
600 V
Overvoltage category
III
Pollution degree
2
L s Clearance distance
‌ 43.3 mm
K s Creepage distance
‌ 49 mm
Tightening torque
‌4 Nm (2x steel screw M5)

Version

Field of application
Industrial version
Termination
Spring clamp termination
Pack contents
Connecting cable included

Commercial data

Packaging size
1
Net weight
161.25 g
Country of origin
Germany
European customs tariff number
90303370
ECl@ss
27210902 Current transformer

Specifications and approvals

Specifications
EN 50178 || IEC 61373
Approvals
DNV GL
CE
Yes

Material properties

Material (hood/housing)
Polycarbonate (PC)
Material flammability class acc. to UL 94
V-0
RoHS
compliant with exemption
ELV status
compliant with exemption
China RoHS
50
REACH Annex XVII substances
No
REACH ANNEX XIV substances
No
REACH SVHC substances
Lead

Identification

Series
HCM
Element
Current sensor
Sensor technology
Hall-Effekt || Closed loop
Features
Hall effect compensated current sensor || Measurable currents: AC, DC, pulsed, mixed ... || High accuracy over the entire measuring range || Galvanic insulation between primary and secondary current || Switchboard mounting || Housing material and potting mass have a flammability rating UL 94 V-0 || Applications: frequency converters, electrical drives, switched mode power suppplies, UPS