Harting

20310300302

Current sensor, Industrial version, IPM Primary current, measuring range: ‌0 ... ±,500 A, KN Turns ratio: 1 : 2000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Technical characteristics

I PN Nominal primary current
300 A
I PM Primary current, measuring range
[‌0] ... [±500 A]
R M Measuring resistance @ I PM max , U C max , T A max
1 ... ‌40 Ω For other primary currents see diagram.
I SN Nominal secondary current
150 mA
K N Turns ratio
1 : 2000
U C Power supply
±12 ... ±20 V ±5 %
I C Current consumption @ U C min
26 mA + I
X Overall accuracy @ I PN , T A = 25 °C
± 0.5 %
Ε L Linearity
< 0.1 %
I O Offset current @ I P = 0 A, T A = 25 °C
± 0.2 mA
I OT maximum temperature drift of I O
± 0.7 mA
T r Response time @ I PN
< 1 µs
Di/dt with optimal coupling
> 100 A/µs
F Frequency
0 ... 100 kHz
T A Ambient temperature
-40 ... +85 °C
T S Storage temperature
-45 ... +90 °C
R S Secondary coil resistance @ T A max
28 Ω
U D Test voltage, effective (50 Hz, 1 min)
3 kV Primary - secondary
U St Rated impulse voltage (1,2/50 µs)
10 kV
U B Rated voltage
600 V
Overvoltage category
III
Pollution degree
2
L s Clearance distance
‌ 17.8 mm
K s Creepage distance
‌ 18.5 mm
Tightening torque
‌3.2 Nm (2x steel screw M4 - Vertical) || ‌3.2 Nm (4x steel screw M4 - Horizontal)

Version

Field of application
Industrial version
Termination
3x steel screw M4

Commercial data

Packaging size
1
Net weight
132.8 g
Country of origin
Germany
European customs tariff number
90303370
ECl@ss
27210902 Current transformer

Specifications and approvals

Specifications
EN 50178 || IEC 61373
Approvals
DNV GL
CE
Yes

Material properties

Material (hood/housing)
Polycarbonate (PC)
Material flammability class acc. to UL 94
V-0
REACH Annex XVII substances
No
REACH ANNEX XIV substances
No

Identification

Series
HCM
Element
Current sensor
Sensor technology
Hall-Effekt || Closed loop
Features
Hall effect compensated current sensor || Measurable currents: AC, DC, pulsed, mixed ... || High accuracy over the entire measuring range || Galvanic insulation between primary and secondary current || Switchboard mounting || Housing material and potting mass have a flammability rating UL 94 V-0 || Applications: frequency converters, electrical drives, switched mode power suppplies, UPS