Technical characteristics

I PN Nominal primary current
800 A
I PM Primary current, measuring range
[‌0] ... [±1.000 A]
U C Power supply
±15 V ±5 %
U OUT Output voltage @ I PN
4 V
R L Load resistance
> 1 kΩ
I C Current consumption @ U C min
25 mA
R IN Insulation resistance
> 500,000 kΩ
X Overall accuracy @ I PN , T A = 25 °C
± 1 %
Ε L Linearity
< 0.5 %
U O Offset voltage@ I P = 0 A, T A = 25 °C
± 10 mV
U OOL Offset after I Pmax
± 10 mV
U OT maximum temperature drift of U O
± 1 mV/K
U outT thermal gain drift
± 0,05 %/K
T r Response time @ I PN
< 3 µs
Di/dt with optimal coupling
> 50 A/µs
F Frequency
0 ... 50 kHz
T A Ambient temperature
-25 ... +85 °C
T S Storage temperature
-25 ... +90 °C
U D Test voltage, effective (50 Hz, 1 min)
3.5 kV Primary - secondary
U B Rated voltage
690 V
L s Clearance distance
‌ 22.7 mm
K s Creepage distance
‌ 36.6 mm
Tightening torque
‌3.2 Nm (2x steel screw M4 - Vertical)

Version

Field of application
Industrial version
Termination
Metz Typ 320 (PT11504VBBN)
Pack contents
Counter connector included

Commercial data

Packaging size
1
Net weight
236 g
Country of origin
Germany
European customs tariff number
90303370
ECl@ss
27210902 Current transformer

Specifications and approvals

Specifications
EN 50178 || IEC 61373
Approvals
DNV GL
UL / CSA
UL 508 NMTR2.E359667 || CSA-C22.2 No. 14-13 NMTR8.E359667

Material properties

Material (hood/housing)
Polycarbonate (PC)
Material flammability class acc. to UL 94
V-0
RoHS
compliant
ELV status
compliant
China RoHS
e
REACH Annex XVII substances
No
REACH ANNEX XIV substances
No
REACH SVHC substances
No

Identification

Series
HCME
Element
Current sensor
Sensor technology
Hall-Effekt || Open loop
Features
Hall effect compensated current sensor || Measurable currents: AC, DC, pulsed, mixed ... || Galvanic insulation between primary and secondary current || Switchboard mounting || Housing material and potting mass have a flammability rating UL 94 V-0 || Applications: frequency converters, electrical drives, auxiliary converters