Honeywell

AQ25242B/U

Aquatrol® universal injection/mixing boiler reset control panel
AQ25242B/U
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Application
Controls one boiler and one mixing (either variable speed injection or floating valve mixing) loop in a hydronic zoning system.
Dimensions (in.)
16 1/2 in wide x 8 in. high x 3 3/8 in deep
Dimensions (mm)
42 cm wide x 20.3 cm high x 8.5 cm deep
Weight (lb)
6.0 lbs
Weight (kg)
2.7 kg
Approvals, Canadian Standards Association
CSA C/US Certified to CSA and UL Standards, File No. LR76030
Tradeline Value
Tradeline
Thermostat Compatibility
AQ1000 Series 2-wire communicating thermostats and most digital thermostats
Setback Program
7 day, up to 2 setback periods/day.
User Interface
LCD Display and a 7 button Key Pad
Number of Zones
4
Zoning Devices Controlled
Zone pumps or 2-wire valves (line voltage)
Boiler Control Temperature (F)
Supply--Max: OFF, 120F to 225 F; Min: OFF, 59F to 180F; Differential--2 F to 41 F or Auto (minimum 2 minutes on time)
Boiler Control Temperature (C)
Supply--Max: OFF, 49C to 107 C; Min: OFF, 15C to 82C; Differential--1 C to 23 C or Auto (minimum 2 minutes on time)
Boiler Design Temperature (F)
80F to 210F
Boiler Design Temperature (C)
26C to 99C
Outdoor Low Design Control Temperature (F)
-60F to 32F
Outdoor Low Design Control Temperature (C)
-51 C to 0 C
Return Min. Control Temperature (F)
80 F to 180 F
Return Min. Control Temperature (C)
27C to 82C
Boiler Heat Post Purge
Off, 10 seconds to 30 minutes (factory default is 30 seconds)
Pump/Valve exercise
30 seconds per 2 weeks of space heating inactivity
R-C Output (on transformer)
38 VA, 24 Vac Class II
R-C Input (on Control and Zoning Modules)
24 Vac Class II (input on Control and Zoning Modules)
Demand Input
Heat Demand (Thermostat R-W), Auxiliary Demand, and DHW Demand--External dry contacts connection only
B-B Communication Bus Terminals
Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules.
Zone Module Thermostat Input
Low voltage, Class II, 2-wire polarity-insensitive, digital communicating with power link to AQ1000 series thermostat.
Output Ratings
Boiler (T-T)-- 24 Vac, 0.5A, 12VA; Auxiliary Low Voltage-- 24 Vac, 0.5A, 12VA; Boiler Pump-- 120 Vac/250 Vac 5A, 1/3HP; DHW Pump/Valve-- 120 Vac 5A, 1/3HP; Auxiliary Pump-- Dry contact output, 120 Vac/250 Vac 5A, 1/3 HP
Zone Output Contact Rating
Pumps: 120 Vac/250 Vac, 5A, 1/3 HP,Valves: 24 Vac, 0.5 A, 12 VA
Mixing Valve Floating Output (Com,O,C)
24 Vac rated dry contacts
Mixing Valve Modulating Output
0-10 Vdc
Secondary Pump Output Rating
120 Vac 5A, 1/3HP
Variable Speed Injection Pump Output
Triac modulated; 120 Vac, 2.1A, 1/6HP
Electrical Connections
Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals
Operating Humidity Range (% RH)
5 to 90% RH, non-condensing
Secondary Loop Temperature Range (F)
Mixing (Supply) max control--80 F to 210 F; Mixing (Supply) min control--35 F to 150 F; Mixing (Supply) Design Temperature--70 F to 210 F; Return min control--80 F to 180 F
Secondary Loop Temperature Range (C)
Mixing (Supply) max control--27 C to 99 C; Mixing (Supply) min control--2 C to 66 C; Mixing (Supply) Design Temperature--21 C to 99 C; Return min control--27 C to 82 C
WWSD (Warm Weather Shut Down) Temperature (F)
Off, 35 F to 100 F
WWSD (Warm Weather Shut Down) Temperature (C)
Off, 1 C to 38 C
Sensor
Supply/Return Sensor--10 kilohm NTC thermistor at 25 C (77 F) ±0.5F (±0.3C) up to 500 ft (150 M) using 18 AWG or larger wire, Lead Length: 10 ft. (3050 mm); Outdoor Sensor--10 kilohm NTC thermistor at 25 C (77 F) ± 0.5F (±0.3C) up to 500 ft (150 M) using
Replacement Parts
AQ10X38 24 Vac 38 VA transformer,AQ15540B 4-zone pump expansion module,AQ12C11 supply/return/mixed loop sensor,AQ12C10 outdoor sensor,AQ15200B universal injection/mixing boiler reset module
Temperature Ratings (C)
Panel--0 C to 55 C; Sensor-- -50 C to +110 C
Temperature Ratings (F)
Panel--32 F to 130 F; Sensor-- -58 F to +230 F
Supply Voltage
120V 60 Hz

Documents

Data Sheet

Download

Related products