Specifications
- Product Type
- Twist-lock
- Product Item
- Connector Body
- Wiring Scheme
- 3-Pole, 4-Wire Grounding
- Amperage
- 30A
- Voltage
- 3 Phase 480V AC
- NEMA Configuration
- L16-30R
- Item Style
- Chem/Marine
- Device Color
- Yellow
- Cord Dia.
- .35"-1.15" (9-29)
- Terminal Retainer Material
- Clear polycarbonate
- Housing Material
- Yellow nylon
- Cord Clamp Material
- Yellow nylon
- Terminal Clamp Material
- .08" (2) steel-nickel plated
- Terminal Screw Material
- #10-32 Bronze (white finish on neutral screw when used) Multi-drive
- Ground Screw Material
- #10-32 Bronze (green finish) Multi-drive
- Cord Clamp Screw Material
- Stainless steel, Multi-drive
- Body Holding Screw Material
- Stainless steel, Multi-drive
- Body Contact Carrier Material
- Natural White Nylon
- Contact Spring Material
- Brass
- Spring Binding Plate Material
- Brass
- Ground Contact Material
- .031" (.8) Brass
- Ratings
- Molded In or Stamped On
- Catalog No
- Permanently ink marked on product
- Dielectric Voltage Withstand
- 2,000V minimum
- Current Interrupting
- Certified for current interrupting at full rated current
- Temperature Rise
- Max 30C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of .75.
- Cord Accommodation
- Round portable service cords of diameters commensurate with the device rating as defined in UL Standard 62, CSA C22.2 No. 49.
- Terminal Accommodation
- 30A #10 AWG
- Terminal Identification
- Terminals identified in accordance with UL 498 (X, Y, Z, White, Green)
- Flammability
- HB or better per UL 94 or CSA 22.2 No. 0.6
- Operating Temperatures
- Maximum Continuous 75 C Minimum -40 C (w/o impact)
- Moisture Resistance
- IP20
- Listings
- FED SPEC UL/CSA
- Weight in LBs
- 0.4
Ordering Information
- Cord Diameter
- .350"-1.150" (9-29)
Electrical
- Current Interrupting
- Certified for current interrupting at full rated current
- Dielectric Voltage
- Withstands 2,000V minimum
Mechanical
- Terminal Accommodation
- #16 AWG - #8 AWG stranded copper wire only.
- Terminal Identification
- Terminals identified in accordance with UL 498
Environmental
- Flammability
- HB or better per UL94 or CSA 22.2 No. 0.6
- Moisture Resistance
- IP20 Suitability
- Operating Temperatures
- Maximum Continuous 75°C Minimum -40°C (w/o impact)
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther