Every Hubbell non-metallic Pin and Sleeve product is designed to meet the International Standard IEC 60309-1 and IEC 60309-2. This device standard calls out singly rated, non-interchangeable configuration for every voltage and type of service.
HBL330B6W
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Terminal Accommodations
#12 To #8 AWG copper wire only
Temperature Rise
Max 30° C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%.
Mounting Flange
Zytel 101 Nylon
Endurance
5,000 connect and disconnect cycles with load for 16A and 20A, 1,000 cycles with load and 1,000 cycles w/o load for 30A, 32A, 60A and 63A, and 250 cycles with load and 250 cycles w/o load for 100A and 125A.
Dielectric Withstand Voltage
Withstands 3,000V AC Min.
Poles and Wires
2 Pole, 3 Wire
Impact Resistance
Per CSA C22.2 No. 182.1 / UL1682.
Housing
Zytel 101 Nylon
Color
blue
Terminal Screws
Stainless Steel (300 series)
Retainer
High-Impact Thermoset
Moisture Resistance
Watertight per IEC 60309-1
Assembly Screws
Stainless Steel (300 series)
Mounting Screws
Stainless Steel (300 Series)
Service Style
Standard
Certifications
UL Listed, UL Standard 498 CSA Certified to CSA Spec. C22.2 No. 182.2 UL Classified to IEC 309-1 and IEC 309-2.
Weight in LBs
0.95
Gaskets
Solid Neoprene
Voltage
250V
Max Working Voltage
600V RMS (i.e.minimum creepage distance 10 mm minimum)
Certification
UL Listed, File E146032 Receptacles and Inlets, E146033 Plugs and Connectors, UL Standard UL1682 & UL1686C2, CSA Certified File LR280C for Plugs, Connectors and Inlets, LR285C for Receptacles, CSA Standard C22.2 No. 182.1, UL Classified to IEC60309-1, IEC
Flammability
HB or Better per UL 94 or CSA C22.2 No. 0.17
Ground/Phase Pins
Brass
Product Type
iec-devices
Ingress Protection
IP 67 Suitability
Contact Carrier
High-Impact Thermoset
Replacement Interior Number
IN330BM
Amperage
30A
Terminal Identification
Terminals identified in accordance with North American and IEC conventions.
Device
Inlet
Lock Ring
Rynite SST35
Current Interrupting
Certified for current interrupting at full rated current.
IEC Product Type
Watertight
Operating Temperatures
Maximum Continuous: 75° C; Minimum Continuous: -40° C w/o impact.
Product Identification
Identification and ratings are a permanent part of the device housing.

Related products