Every Hubbell non-metallic Pin and Sleeve product is designed to meet the International Standard IEC 60309-1 and IEC 60309-2. This device standard calls out singly rated, non-interchangeable configuration for every voltage and type of service.
HBL4100P5W
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Additional Information

Part Number
HBL4100P5W
UPC
783585404035
UNSPSC
39121402
Country of Origin
PR

Specifications

Terminal Identification
Terminals identified in accordance with North American and IEC conventions.
Contact Carrier
High-Impact Thermoset
Lock Ring
Rynite SST35
Terminal Screws
Stainless Steel (300 series)
Product Type
iec-devices
Temperature Rise
Max 30° C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%.
Grommet/Glands
Solid Neoprene
Operating Temperatures
Maximum Continuous: 75° C; Minimum Continuous: -40° C w/o impact.
Replacement Interior Number
IN4100DM
Terminal Accommodations
#3 To #1/0 AWG copper wire only
Dielectric Withstand Voltage
Withstands 3,000V AC Min.
Certification
UL Listed, File E146032 Receptacles and Inlets, E146033 Plugs and Connectors, UL Standard UL1682 & UL1686C2, CSA Certified File LR280C for Plugs, Connectors and Inlets, LR285C for Receptacles, CSA Standard C22.2 No. 182.1, UL Classified to IEC60309-1, IEC
Device
Plug
Product Identification
Identification and ratings are a permanent part of the device housing.
Housing
Zytel 801 Nylon
Endurance
5,000 connect and disconnect cycles with load for 16A and 20A, 1,000 cycles with load and 1,000 cycles w/o load for 30A, 32A, 60A and 63A, and 250 cycles with load and 250 cycles w/o load for 100A and 125A.
Impact Resistance
Per CSA C22.2 No. 182.1 / UL1682.
Retainer
High-Impact Thermoset
Amperage
100A
Flammability
HB or Better per UL 94 or CSA C22.2 No. 0.17
Color
black
Weight in LBs
3.95
Poles and Wires
3 Pole, 4 Wire
Cord clamp range
1.065" To 1.940"
Cord Clamps
Rynite SST35
Gland Cap
Rynite SST35
Cord Accommodation
Round portable service cords of diameters commensurate with the device rating as defined in UL Standard 62, CSA C22.2 No. 49 and the harmonized European Standards.
Certifications
UL Listed, File E146032 Receptacles and Inlets, E146033 Plugs and Connectors, UL Standard UL1682 & UL 1686C2, CSA Certified File LR280C for Plugs, Connectors and Inlets and LR285C for Receptacle CSA Standard C22.2 No. 182.2, UL Classified to IEC 309-1 and
Ground/Phase Pins
Brass
Assembly Screws
Stainless Steel (300 series)
Ingress Protection
IP 67 Suitability
Service Style
Standard
Voltage
3 Phase 600V
Clamp Nut
Nickel Plated Brass
IEC Product Type
Watertight
Current Interrupting
Certified for current interrupting at full rated current.
Cord Grip Retention
Per CSA C22.2 No. 182.1 / UL1682.
Max Working Voltage
600V RMS (i.e.minimum creepage distance 10 mm minimum)
Moisture Resistance
Watertight per IEC 60309-1
Cord Clamp Screws
Stainless Steel (300 Series)