Every Hubbell non-metallic Pin and Sleeve product is designed to meet the International Standard IEC 60309-1 and IEC 60309-2. This device standard calls out singly rated, non-interchangeable configuration for every voltage and type of service.
HBL460B5W
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Certification
UL Listed, File E146032 Receptacles and Inlets, E146033 Plugs and Connectors, UL Standard UL1682 & UL1686C2, CSA Certified File LR280C for Plugs, Connectors and Inlets, LR285C for Receptacles, CSA Standard C22.2 No. 182.1, UL Classified to IEC60309-1, IEC
Operating Temperatures
Maximum Continuous: 75° C; Minimum Continuous: -40° C w/o impact.
Weight in LBs
1.85
Gaskets
Solid Neoprene
Replacement Interior Number
IN460DM
Flammability
HB or Better per UL 94 or CSA C22.2 No. 0.17
Amperage
60A
Terminal Identification
Terminals identified in accordance with North American and IEC conventions.
Color
black
Device
Inlet
Temperature Rise
Max 30° C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%.
Product Type
iec-devices
Terminal Screws
Stainless Steel (300 series)
Housing
ZytelÒ 101 Nylon
Lock Ring
Rynite SST35
Mounting Screws
Stainless Steel (300 Series)
Mounting Flange
Zytel 101 Nylon
Poles and Wires
3 Pole, 4 Wire
Terminal Accommodations
#8 To #2 AWG copper wire only
Product Identification
Identification and ratings are a permanent part of the device housing.
Retainer
High-Impact Thermoset
Moisture Resistance
Watertight per IEC 60309-1
Max Working Voltage
600V RMS (i.e.minimum creepage distance 10 mm minimum)
Impact Resistance
Per CSA C22.2 No. 182.1 / UL1682.
Ground/Phase Pins
Brass
IEC Product Type
Watertight
Service Style
Standard
Contact Carrier
High-Impact Thermoset
Ingress Protection
IP 67 Suitability
Assembly Screws
Stainless Steel (300 series)
Dielectric Withstand Voltage
Withstands 3,000V AC
Certifications
UL Listed, UL Standard 498 CSA Certified to CSA Spec. C22.2 No. 182.2 UL Classified to IEC 309-1 and IEC 309-2.
Current Interrupting
Certified for current interrupting at full rated current.
Endurance
5,000 connect and disconnect cycles with load for 16A and 20A, 1,000 cycles with load and 1,000 cycles w/o load for 30A, 32A, 60A and 63A, and 250 cycles with load and 250 cycles w/o load for 100A and 125A.
Voltage
3 Phase 600V

Related products