Specifications

Input Voltage (V)
190 to 240VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz
Output Form
DPDT
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
Restart Delay Range
After a Fault or Complete Power Loss: 2s
Trip Delay Range
Low Voltage: 4s; Unbalance Phasing Faults: 2s
Trip Point Accuracy (%)
±1%
Undervoltage Trip Voltage
90%
Undervoltage Reset Voltage (%)
93%
Voltage Unbalance Trip Point (%)
6%
Voltage Unbalance Reset (%)
4.50%
Termination Type
Torque: 12 in-lbs; Wire: Stranded or solid 10-22AWG
Mounting Method
DIN rail or surface mount (plug-in to OT11-PC socket)
Operating Temperature
-40° to 70°C (-40° to 158°F)
Humidity
95% non-condensing per IEC 68-2-3
Dimensions
1.75 in H x 2.38 in W x 4.13 in D (44.5 x 60.3 x 104.8 mm)
Weight (lbs/g)
0.65 lb. (10.4 oz. 294.8 g)

Documents

Data Sheet

Download