Littelfuse

TVM208A100.5S3S

TVM208A100.5S3S - TVM Series
TVM208A100.5S3S
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
208VAC
Input Type
3-phase delta or wye with no connection to neutral
Input AC Line Frequency (Hz)
50-100Hz
Input Phase Sequence
ABC
Output Type
Isolated SPDT relay contacts
Output Load Rating (VA)
10A resistive @ 125VAC; 5A @ 250VAC; 1/4hp @ 125VAC
Reset Time (ms)
Automatic
Response Time (ms)
Phase loss: ≤200ms; Phase reversal: ≤200ms
Restart Delay Range
3s fixed
Restart Delay Tolerance (%)
±15% or ±0.2s whichever is greater
Trip Delay Range
0.5s fixed
Trip Delay Tolerance (%)
±15% or ±0.1s whichever is greater
Trip Delay vs Temperature
Trip variation: ≤±2%
Overvoltage Trip Voltage (%)
109 - 113% of the adjusted line voltage
Overvoltage Reset Voltage (%)
≅-3% of the trip voltage
Undervoltage Trip Voltage
88-92% of the adjusted line voltage
Undervoltage Reset Voltage (%)
≅+3% of the trip voltage
Voltage Unbalance Trip Point (%)
10% fixed
Voltage Unbalance Reset (%)
≅-0.7% unbalance
Phase Loss
≥25% unbalance
Power Consumption
≅2W
Dielectric Breakdown
≥1500V RMS input to output terminals
Surge Protection
IEEE C62.41-1991 Level B
Type of Detection
Voltage detection with delayed trip and automatic reset
Life
Mechanical - 1 x 106; Electrical - 1 x 105
Termination Type
0.25 in. (6.35mm) male quick connect terminals
Mounting Method
Suface mount with one #8 (M5 x 0.8) screw
Operating Temperature
-40° to 55°C (-40°F to 131°F)
Storage Temperature (F/C)
-40° to 85°C (-40°F to 185°F)
Humidity
95% relative non-condensing
Dimensions
2.00 x 2.00 x 1.25 in. (50.8 x 50.8 x 31.8mm)
Weight (lbs/g)
≅2.8oz (79g)

Documents

Data Sheet

Download