MY2 AC100/110

Standard type, Single, Plug-in terminal, 24 VDC 5 A (Resistive load), 220 VAC 5 A (Resistive load), Output DPDT (5 A 24 V)
MY2 AC100/110
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Ratings

Product Classification
Monostable Relays, Standard Type
Coil Ratings
100 Vac 11.7 Ma (50 Hz) / 100 Vac 10 Ma (60 Hz) / 110 Vac 12.9 Ma (50 Hz) / 110 Vac 11 Ma (60 Hz)
Coil Resistance
3750 Ω
Operate Voltage (Set Voltage)
80 % Max.
Release Voltage (Reset Voltage)
30 % Min.
Max. Voltage
110 % Max. (Of Rated Voltage)
Power Consumption
Approx. 0.9 To 1.3 Va (60 Hz)
Contact Type
Dpdt
Contact Method
Single
Contact Material
Ag
Contact Rated Load
220 Vac 5 A (Resistive Load), 220 Vac 2 A (Inductive Load (Cos Φ= 0.4)), 24 Vdc 5 A (Resistive Load), 24 Vdc 2 A (Inductive Load (L/R = 7 Ms))
Maximum Switching Voltage
250 Vac,125 Vdc
Maximum Switching Current
Ac: 5 A, Dc: 5 A
Failure Rate
1 Ma At 5 Vdc (Failure Level: P Reference Value) (Switching Frequency Of 120 Operations Per Minute)
Ambient Temperature (Operating)
-55 To 70 ℃ (With No Icing Or Condensation)
Ambient_Humidity (Operating)
5 To 85%Rh (With No Icing Or Condensation)
Contact Resistance
50 Mω Max., Measuring The Voltage Drop Across The Contacts By Applying Test Voltage/Current As 5 Vdc 1 A
Release Time (Reset Time)
20 Ms Max. (The Operate Or Release Time Was Measured With The Rated Voltage At An Ambient Temperature Of 23 ℃)
Insulation Resistance
Between Coil And Contacts: 100 Mω Min. (At 500 Vdc), Between Contacts Of Different Polarity: 100 Mω Min. (At 500 Vdc), Between Contacts Of Same Polarity: 100 Mω Min. (At 500 Vdc)
Dielectric Strength
Between Coil And Contacts: 2000 Vac (50/60 Hz 1 Min), Between Contacts Of Different Polarity: 2000 Vac (50/60 Hz 1 Min), Between Contacts Of Same Polarity: 1000 Vac (50/60 Hz 1 Min)
Vibration Resistance (Destruction)
10 To 55 To 10 Hz, 0.5-Mm Single Amplitude (1-Mm Double Amplitude)
Vibration Resistance (Malfunction)
10 To 55 To 10 Hz, 0.5-Mm Single Amplitude (1-Mm Double Amplitude)
Shock Resistance (Destruction)
1000 M/S**2
Shock Resistance (Malfunction)
200 M/S**2
Endurance (Mechanical)
50 Million Operations Min. (Switching Frequency 18,000 Operations/H)
Endurance (Electrical)
500,000 Operations Min. (23 ℃, Rated Load, Switching Frequency 1,800 Operations/H)
Protective Structure
Closed Type (Cover)
Terminal Structure
Plug-In Terminal
Weight
Approx. 35 G

Specifications

Coil Ratings
100 Vac 11.7 Ma (50 Hz) / 100 Vac 10 Ma (60 Hz) / 110 Vac 12.9 Ma (50 Hz) / 110 Vac 11 Ma (60 Hz)
Contact Type
Dpdt
Contact Method
Single
Contact Material
Ag
Contact Rated Load
220 Vac 5 A (Resistive Load)
Contact Rated Load
220 Vac 2 A (Inductive Load (Cos Φ= 0.4))
Contact Rated Load
24 Vdc 5 A (Resistive Load)
Contact Rated Load
24 Vdc 2 A (Inductive Load (L/R = 7 Ms))
Maximum Switching Current
Ac: 5 A, Dc: 5 A
Terminal Structure
Plug-In Terminal

Documents

Data Sheet

Download

Related products